3M 5797A-MT Manual De Usuario

Descargar
Página de 12
Cold Shrink QS-III 
Three-Conductor Splice Kit for use on
Armor and Non-Armor Cables
Instructions
IEEE Std. 404
35 kV Class
250 kV BIL
* Splices (including size transitions) can be made to smaller or larger conductors, provided 
both cables are within the Insulation O.D. Range and the connector meets the dimensional 
requirements shown below.
Connector Dimensional Requirements 
Minimum
Maximum
inches (mm)
inches (mm)
Outside Diameter
0.51" (13,0 mm)
1.70" (43,2 mm)
Length
Aluminum (Al/Cu)
------
6.00" (152 mm)
Length
Copper (Cu)
------
6.50" (165 mm)
Cable Range Requirements 
Kit Number
Cable Insulation
Conductor
O.D. Range
Size Range
5797A-MT
1.07" to 1.70"
1/0 AWG - 350 kcmil*
(27,2 mm to 43,2 mm)
(60 - 185 mm
2
)
3M
Cold Shrink
QS-III Splicing Kit
5797A-MT
78-8126-0432-6-A
CAUTION
Working around energized high-voltage systems may cause serious
injury or death. Installation should be performed by personnel familiar
with good safety practice in handling high-voltage electrical equipment.
De-energize and ground all electrical systems before installing product.