Bard T**H*D Manual De Usuario

Descargar
Página de 19
Manual 2100-516H 
Page 
3 of 19
TABLE  1
DIAGRAM TO USE WITH UNIT AND VENTS
System
Vent
None
CRV, ERV, MFAD
CRVMWH-3
CHCRV-5
EIFM 
Economizer
ECONWM*
CS2000A*
Vent Code
X
R, M, V, P
C
E
T, W, S
Thermostat Programmable Programmable Programmable Programmable Programmable
All
Model Series
No
Yes
No
Yes
No
Yes
No
Yes
No
Yes
Heat Pump
S**H
T**H
W**H
1
1
3 & 4
2
15
14
N/A
5
N/A
13
11
Heat Pump with
Dehumidification
S**H*D
T**H*D
W**H*D
7
6
9 & 10
8
N/A
14
N/A
12
N/A
13
N/A
NOTE:  The voltage should be measured at the field power
connection point in the unit and while the unit
is operating at full load (maximum amperage
operating condition).
WIRING – LOW VOLTAGE WIRING
230/208V, 1 phase and 3 phase equipment dual primary 
voltage transformers.  All equipment leaves the factory 
wired on 240V tap.  For 208V operation, reconnect 
from 240V to 208V tap.  The acceptable operating 
voltage range for the 240V and 208V taps are:
TABLE  3
WALL THERMOSTAT
TABLE  2
OPERATING VOLTAGE RANGE
An 18 gauge copper, color-coded thermostat cable is 
recommended.  The connection points are shown in this 
Manual.  See Table above.
Low Voltage Connection
These units use a grounded 24-volt AC low voltage 
circuit.  
The “R” terminal is the hot terminal and the “C” 
terminal is grounded.
G” terminal is the 
fan input.
Y” terminal is the 
compressor input
B” terminal is the 
reversing valve input.  The reversing 
valve must be energized for heating mode.
R” terminal is the 24 VAC hot.
C” terminal is the 24 VAC grounded.
LOW VOLTAGE CONNECTIONS
FOR DDC CONTROL
  
Fan Only 
Energize G
  
Cooling Mode 
Energize Y, G
  
Heat Pump Heating 
Energize Y, G, B
  
2nd Stage Heating 
Energize G, W2, Y, B
  
w/Heat Pump (if employed)
  
Ventilation 
Energize G, O1
  
Emergency  Heat 
Energize B, W2, E, G
Dehumidification
Energize W3
L” terminal is 
compressor lockout output.  This 
terminal is activated on a high or low pressure trip by the 
electronic heat pump control.  This is a 24 VAC output.
W2” terminal is second stage heat (if equipped).
O1” terminal is the 
ventilation input.  This terminal 
energizes any factory installed ventilation option.
E” terminal is the 
emergency heat input.  This terminal 
energizes the emergency heat relay.
W3” terminal is the 
dehumidification input.  This 
terminal energizes compressor, blower and three-way 
valve.
TAP
RANGE
240V
253 – 216
208V
220 – 187
Part Number
Predominate Features
8403-058
(TH5220D1151)
2 stage Cool, 2 stage Heat - Conventional 
1 stage Cool, 2 stage Heat - Heat Pump 
Electronic Non-Programmable 
Auto or Manual changeover
8403-060
(1120-445)
3 stage Cool; 3 stage Heat
Programmable/Non-Programmable Electronic
HP or Conventional
Auto or Manual changeover
Dehumidification Output