Cisco Nexus 7000 6.0kW AC Power Supply Module N7K-AC-6.0KW Hoja De Datos

Los códigos de productos
N7K-AC-6.0KW
Descargar
Página de 8
 
 
Data Sheet 
© 2008-2009 Cisco Systems, Inc. All rights reserved. This document is Cisco Public Information. 
Page 3 of 8 
Table 2. 
Available Output Based on Input Power 
Number of Inputs 
Input Power* 
Output Power 
Single input 
220V 
3750W 
Dual input 
220V 
7500W 
* Only a high line input is supported. 
Cisco Nexus 7000 Series Power Supply Redundancy 
The Cisco Nexus 7000 Series Chassis supports multiple load-sharing, fault-tolerant, and hot-
swappable power supplies. As few as just one power supply can be used to operate a chassis. 
Using multiple power supplies provides additional power capacity and resilience after failure of the 
power supply, the generating supply itself, or a facility component such as a Uninterruptible Power 
Supply (UPS) or a circuit breaker. 
Cisco Nexus 7000 Series systems can operate in four user-configurable power-redundancy 
modes, summarized in Table 3, to meet the redundancy needs of the environment. 
Table 3. 
Power Redundancy Modes 
Redundancy Mode 
Description 
Combined 
No redundancy; power available to the system is the sum of power outputs of all power 
supplies in the chassis 
Power supply redundancy 
(N+1) 
Guards against failure of one of the power supplies; power available to the system is the 
sum of the two least-rated power supplies 
Input source redundancy 
(grid redundancy) 
Guards against failure of one input circuit (grid); for grid redundancy, each input on the 
power supply is connected to an independent AC feed, and power available to the system is 
the minimum power from either of the input sources (grids) 
Power supply and input 
source redundancy 
(full redundancy) 
System default redundancy mode; guards against failure of either one power supply or one 
AC grid, and power available is always the minimum of input source and power supply 
redundancy 
The total amount of power available to the Cisco Nexus 7000 Series system depends on the types 
of power supplies installed, the number of connected inputs, and the configured power supply 
redundancy mode. Table 4 shows the maximum available power for each redundancy mode for 
the 6.0kW and 7.5kW power supplies. 
Table 4. 
Maximum Total Output Power by Redundancy Mode 
Power Supply Redundancy Mode 
Power Supply Type 
Number of 
Power 
Supplies 
Combined 
N+1 
Grid 
Full 
6000W 
6000W* 
6000W* 
6000W* 
12,000W 
6000W 
6000W 
6000W 
18,000W 
12,000W 
9000W 
9000W 
6.0kW 
24,000W 
18,000W 
12,000W 
12,000W 
7500W 
7500W* 
7500W* 
7500W* 
15,000W 
7500W 
7500W 
7500W 
22,500W 
15,000W 
11,250W 
11,250W 
7.5kW 
30,000W 
22,500W 
15,000W 
15,000W 
Note:  