Guardian Technologies 02010-2 Manual De Usuario

Descargar
Página de 56
 
 
9
Section 2 – Operation
Recreational Vehicle Generator
NOTE:
If starting from the generator control panel, turn 
OFF loads by setting the generator’s main circuit 
breaker to the OFF (or OPEN) position. If starting 
from a remote panel, turn OFF loads using the 
means provided in the vehicle (such as a main 
circuit breaker). Electrical load circuits will be 
turned ON after the generator has started, stabi-
lized and warmed up.
2.  If the engine has not been started in more than 
two weeks, press the Fuel Pump Primer switch 
and hold it for about 10 to 15 seconds to prime 
the fuel system. However, if the engine is warm, 
skip Step 2.
3.  Hold the engine Start/Stop switch in the  START 
position to crank the engine. Release the switch 
when the engine starts.
  If the engine does not start after it has been 
cranking for 15 seconds, release the Start/Stop 
switch and try again. Holding the switch for 
longer than 15 seconds can damage the starter 
motor.
4.  Let the engine run at no-load for a few minutes to 
stabilize and warm up.
5.  Turn ON electrical loads using the means pro-
vided (such as a main circuit breaker or transfer 
switch).
2.6   STOPPING THE GENERATOR
1.  Turn OFF all electrical loads using the means 
provided (such as a main circuit breaker or 
transfer switch).
2.  Let generator run at no-load for a few minutes, to 
stabilize internal engine generator temperatures.
3.  Place the Start/Stop switch in its STOP position.
2.7   APPLYING LOADS TO GENERATOR
When applying electrical loads to the generator, 
observe these guidelines:
Before applying electrical loads, let the generator 
stabilize and warm up for a minute or two.
DO NOT overload the generator.
2.7.1  LETTING THE ENGINE STABILIZE
The generator supplies correct rated voltage only at 
the proper governed speed. Some electrical appli-
ances may be extremely sensitive to voltage. Incorrect 
voltages can damage such appliances.
If electrical loads are applied at reduced operating 
speeds, such loads imposed on the engine when suf-
ficient power is not available may shorten engine life. 
Never turn ON electrical loads until after the generator 
engine has started and stabilized at no-load.
‹
2.8    SUMMER/WINTER HEAT 
RISER SYSTEM
Under certain weather conditions, it is possible for 
ice to form in the venturi area of the carburetor.  This 
condition can be very dangerous because it can pre-
vent the governor system from functioning properly, 
which results in a “runaway” engine.
The most common weather conditions leading to this 
problem are temperatures in the range of 25° F to 
35° F (-4° C to 1.7° C), along with high humidity. This 
ice formation also can be attributed to the load being 
applied during these weather conditions.  Generators 
running with no-load or light loads applied usually 
have the most problems.
The Summer/Winter Lever (Figure 2.3) should be 
in the WINTER position for ambient temperatures 
below 40° F (4.4° C) and in the SUMMER position for 
ambient temperatures above 40° F (4.4° C).
Figure 2.3 – Heat Riser System
When the heat riser is in the SUMMER (down) posi-
tion (Figure 2.2), air is drawn into the air cleaner 
from the upper intake tube.
When the heat riser is in the WINTER (up) position, 
air is drawn from the lower intake tube, which is 
positioned to draw the heated air near the exhaust 
manifold.
To prevent carburetor icing, the owner/operator 
should physically position the heat riser to the prop-
er position dependent on the temperature.