HORIZONTAL EXAMPLES FOR COLINEAR DIRECT VENT
Figure 27
Enhanced top view of Figure 26
Figure 26
Max Vent Run - 40 ft. Equivalent With Three (3) 90° Elbows
Special Note: The vent terminal 90° elbow and first 90° elbow
off back of the heater, when within 6” (15.2 cm), do not con-
tribute to the overall vent length measurement. For each 45° 
elbow installed in the horizontal run, the length of the hori-
zontal run MUST be reduced by 1.5 feet (45 cm). This does
not apply if the 45° elbows are installed on the vertical part of 
the vent system. Reduce the length of the horizontal run 3 feet
(91.4 cm) for every 90° elbow.
Note: 
On horizontal runs, a P.V.C. support clamp needs to be in-
stalled every 3 feet. No “sags” in horizontal vent runs; water will 
settle in the pipe.
When installing a colinear horizontal, the minimum vent length 
protruding from the outside wall is 6” (15.2 cm) for air intake and 
9” for exhaust. See Figure 27.
Note:  Horizontal  discharge  90°  elbow  must  be  pointed  down-
ward. See Figure 26. All horizontal runs require either a 1/4” per 
foot rise to run condensation back to the heater, or a 1/4” per foot 
downward slope to run condensation away from the heater.
Note: All PVC vent run piping can be purchased at a local hard-
ware store. Schedule 40 PVC pipe should be used and cemented. 
PVCA  Horizontal  Colinear  Direct  Vent Adaptor,  PVVTC  Cap, 
PVVK-CFA Flex Kit and PVVK-SH Horizontal Vent Adaptor Kit 
are available from Empire Comfort Systems, Inc. 
Figure 24
In both vertical and horizontal colinear direct vent applications, 
a colinear transition plate model PVCT can be used to minimize 
clearances between intake and exhaust pipes.
For horizontal colinear direct venting, exhaust and intake air, cap 
pipes with 90º elbows, pointed downward.
Note:  If transition plate (model PVCT) is used, the measurement 
for center to center of the pipes will be 2.5”. If the transition plate 
(model PVCT) is not used, the measurement for center to center 
of the pipes can be 3” to 24” maximum.
Note: Must maintain a minimum 3” between 
exhaust outlet and air intake.
EXTERIOR GRADE
12” MIN.
9” MIN.
MIN. 2”
6” MIN.
3” MIN.
Figure 25