Ignition State 
Timing 
Energize Relay and Verify (Closed Circuit) 
15 seconds 
Trial for Ignition 
90 seconds 
Flame Stabilization Period
3 seconds 
Re-energize Relay and Verify 
15 seconds 
Flame Failure Response Time 
1.5 seconds (2 second maximum; 1 second 
minimum) 
De-energize Relay and Verify (Open Circuit) 
15 seconds 
Relay Fault (failed open/close) 
Retry after 2 minutes
Soft Lockout 
Retry after 5 minutes 
ECO Limit Lockout 
Indefinite (See page 11 to reset) 
Verify Resistive Delay 
Retry after 2 minutes (repeats 5 times) 
Simulated Resistive Load Lockout 
Indefinite (cycle power to reset) 
Hardware Error Lockout 
Indefinite (self clears if fault clears for at least 15 
seconds)