Troubleshooting Chart (cont.)
For Models Using Honeywell Gas Control
Five flashes and a three
second pause.
Thermowell fault
Seven flashes and a
three second pause.
Gas control fault detected.
1. Damage to thermowell
    wires.
2. Thermowell sensor resistance
    out of range.
1. Gas control needs to be reset.
2. Gas control is wet or physically
    damaged.
See Service Procedure
AG-III, Page 16
Lite pilot per the instructions
located on the lighting
instructions label or the
lighting instructions located in
the installation and operation
manual.
Eight flashes and a three
second pause.
Pilot flame remains on while gas control is in
the “OFF” position.
Pilot valve stuck in the open position.
Replace gas control.
See Service Procedure
AG-III, Page 18.
Page 5
LED Status
Control Status
Probable Cause
Service
Procedure