Electrical Connection
To properly install your dryer, you must determine the type of 
electrical connection you will be using and follow the instructions 
provided for it here.
If local codes do not permit the connection of a neutral ground 
wire to the neutral wire, see “Optional 3-wire connection” 
section.
This dryer is manufactured ready to install with a 3-wire 
electrical supply connection. The neutral ground wire is 
permanently connected to the neutral conductor (white wire) 
within the dryer. If the dryer is installed with a 4-wire electrical 
supply connection, the neutral ground wire must be removed 
from the external ground conductor screw (green screw), and 
secured under the neutral terminal (center or white wire) of the 
terminal block. When the neutral ground wire is secured under 
the neutral terminal (center or white wire) of the terminal block, 
the dryer cabinet is isolated from the neutral conductor.
A 4-wire power supply connection must be used when the 
appliance is installed in a location where grounding through 
the neutral conductor is prohibited. Grounding through the 
neutral is prohibited for (1) new branch-circuit installations, 
(2) mobile homes, (3) recreational vehicles, and (4) areas 
where local codes prohibit grounding through the neutral 
conductors.
If using a power supply cord:
Use a UL listed power supply cord kit marked for use with clothes 
dryers. The kit should contain:
A UL listed 30-amp power supply cord, rated 120/240 volt 
minimum. The cord should be type SRD or SRDT and be at 
least 4 ft (1.22 m) long. The wires that connect to the dryer 
must end in ring terminals or spade terminals with upturned 
ends.
A UL listed strain relief.
If your outlet looks like this:
4-wire receptacle (14-30R)
Then choose a 4-wire power supply cord with ring or spade 
terminals and UL listed strain relief. The 4-wire power supply cord, 
at least 4 ft (1.22 m) long, must have 4 10-gauge solid copper 
wires and match a 4-wire receptacle of NEMA Type 14-30R. 
The ground wire (ground conductor) may be either green or bare. 
The neutral conductor must be identified by a white cover.
If your outlet looks like this:
3-wire receptacle (10-30R)
Then choose a 3-wire power supply cord with ring or spade 
terminals and UL listed strain relief. The 3-wire power supply cord, 
at least 4 ft (1.22 m) long, must have three 10-gauge solid copper 
wires and match a 3-wire receptacle of NEMA Type 10-30R.
If connecting by direct wire:
Power supply cable must match power supply (4-wire or 3-wire) 
and be:
Flexible armored cable or nonmetallic sheathed copper cable 
(with ground wire), protected with flexible metallic conduit. All 
current-carrying wires must be insulated.  
10-gauge solid copper wire (do not use aluminum).
At least 5 ft (1.52 m) long.
GROUNDING INSTRUCTIONS
SAVE THESE INSTRUCTIONS
  
For a grounded, cord-connected dryer: 
This dryer must be grounded. In the event of malfunction or 
breakdown, grounding will reduce the risk of electric shock 
by providing a path of least resistance for electric current. 
This dryer uses a cord having an equipment-grounding 
conductor and a grounding plug. The plug must be plugged 
into an appropriate outlet that is properly installed and 
grounded in accordance with all local codes and ordinances.
  
For a permanently connected dryer:
This dryer must be connected to a grounded metal, 
permanent wiring system, or an equipment-grounding 
conductor must be run with the circuit conductors and 
connected to the equipment-grounding terminal or lead on 
the dryer.
WARNING:
 
Improper connection of the equipment-
grounding conductor can result in a risk of electric shock.
Check with a qualified electrician or service representative 
or personnel if you are in doubt as to whether the dryer is 
properly grounded. Do not modify the plug on the power 
supply cord: if it will not fit the outlet, have a proper outlet 
installed by a qualified electrician.