Eaton IPC3402-2930 Manual De Usuario
© 2008 Eaton Corporation. All Rights Reserved. All specifications are subject to change without notice.
www.pulizzi.com • pulizzisales@eaton.com • 800-870-2248 • Fax: 605-334-4999
3
CHASSIS
•
19” x 1.72” (1U) x 9.5”
•
Weight approximately 12 lbs.
(IPC3401 & 02)
•
Weight approximately 15 lbs.
(IPC3402-2756
& IPC2930)
•
Detachable mounting brackets allow for
several mounting options
several mounting options
NEMA or IEC 320 OUTLETS
•
IPC3401 has 8 IEC 60320 Type C13
– Rated by UL/CSA 125V~/15A
– Rated by UL/CSA/VDE 250V~/10A
– Rated by UL/CSA 125V~/15A
– Rated by UL/CSA/VDE 250V~/10A
•
IPC3402 has 8 NEMA 5-15R
•
IPC3402-A2 has 8 NEMA 5-20R
•
IPC3402-2756 has 4 NEMA 5-20R
and 4 NEMA 5-15R
and 4 NEMA 5-15R
•
IPC3402-2930 has 8 NEMA 5-15R
(11) INDICATOR LIGHTS
•
Main power to system-CB “on”
•
Individual power “on” to outlets 1-8
•
Data acquisition and remote disable
REMOTE or LOCAL CONTROL
•
Serial RS232 port (DB9 Male) for direct
computer or modem connection
computer or modem connection
•
RS485 input/output for strapping up to
10 systems together over CAT.5 cable
10 systems together over CAT.5 cable
•
Local: one on/off switch for each outlet
•
-NET SYSTEMS ONLY: RJ45 for
network connections (Ethernet)
network connections (Ethernet)
REMOTE DISABLE
•
With the push of a button, disable
remote access to the IPC when needed
remote access to the IPC when needed
POWER SUPPLY
•
The IPC3401 series features a full range
power supply for operation at
100-240VAC input/output
power supply for operation at
100-240VAC input/output
BAUD RATE
•
Default: 9600 baud
EMI/RFI FILTERING
•
Common Mode - Line to Ground
•
Differential Mode - Line to Line
•
Filtered inlet isolates noise before
entering the system
entering the system
•
IPC3402-2756 and IPC3402-2930
do not have filtering
do not have filtering
SPIKE/SURGE SUPPRESSION (TVSS)
•
Line to Line
•
Multi-stage, both MOVs and SAPs
BRANCH CIRCUIT PROTECTION
•
UL498 Listed Main Disconnect Breaker
and guard, with a long time delay curve
provides manual on/off switching and
trips in an overload condition
and guard, with a long time delay curve
provides manual on/off switching and
trips in an overload condition
POWER INPUT
•
IEC 60320 Type C20 EMI/RFI Filtered Inlet
•
Mating power cables must be ordered
separately
separately
•
IPC3402-2756: attached 10’ cable and
NEMA L5-30P
NEMA L5-30P
OUTLET STATUS
•
Query the IPC for Outlet and Watch Dog
status, i.e. outlets are “on” or “off”
status, i.e. outlets are “on” or “off”
STRAPPING
•
Strapping allows up to 10 IPCs
(80 outlets) to be controlled at one address
(80 outlets) to be controlled at one address
•
Units are connected together via the
RS485 “IN” and “OUT” connectors
RS485 “IN” and “OUT” connectors
UNIT NAME / PASSWORD
•
The IPC comes with a default name
@@@@, which can be changed to
any four alphanumeric characters
@@@@, which can be changed to
any four alphanumeric characters
•
Optional 3 character password
MULTIPLE TIME DELAY
TM
(MTD
TM
)
•
Sequence power up and power down to
outlets with a one second time delay
(factory set)
outlets with a one second time delay
(factory set)
•
User Programmable:
– Set power “on” sequence to any
– Set power “on” sequence to any
combination
of
outlets
– Set the MTD
TM
timing from 1 second
to 999 seconds, i.e. 009 = 9 seconds
AUTO-EVENT COMMAND RESPONSE
•
The IPC will automatically update the status
of outlets (“on” or “off”) via serial or telnet
of outlets (“on” or “off”) via serial or telnet
SOFTWARE CONTROLS
•
Multi-platform compatible
•
Control via Terminal Emulation Software
•
Web interface for browser control
COMMANDS AVAILABLE
•
All outlets on/off
•
Specific outlets on/off
•
Set up and Sequence on/off all outlets
•
Create password and unit address
•
Outlet naming (8 characters)
•
Set up, enable or disable Watchdog
•
Display outlet and Watchdog Timer status
•
Automatically receive update outlet
status whenever there’s a change
status whenever there’s a change
•
Auto-reboot outlet 1 with a five second
delay on restart
delay on restart
SPECIFICATIONS:
IPC3401
IPC3401-NET
IPC3402
IPC3402-NET
IPC3402-A2
IPC3402-A2-NET
IPC3402-2756
IPC3402-2930
Approvals
UL/cUL, CE, GS, FCC
UL/cUL, FCC
UL/cUL, FCC
UL/cUL, FCC
UL/cUL, FCC
UL/cUL
UL/cUL
Voltage (50/60Hz)
100-240V~
100-240V~
120V~
120V~
120V~
120V~
120V~
120V~
Current Input
20A @ 120V~
16A @ 240V~
20A @ 120V~
16A @ 240V~
20A
20A
20A
20A
30A
30A
Current Output
16A
16A
16A
16A
16A
16A
24A
24A
Full Load VA
1920VA @ 120V~
3840VA @ 240V~
1920VA @ 120V~
3840VA @ 240V~
1920VA
1920VA
1920VA
1920VA
2880VA
2880VA
Outlets (IEC or NEMA)
Type C13
Type C13
5-15R
5-15R
5-20R
5-20R
(4) 5-20R, (4) 5-15R
(8) 5-15R
Circuit Breaker
20/20A
20/20A
20A
20A
20A
20A
20/10A
20/10A
EMI/RFI Filter
20A
20A
20A
20A
20A
20A
N/A
N/A
Surge Suppression
270V
270V
270V
270V
270V
270V
270V
270V
Power Input
Type C20 Inlet
Type C20 Inlet
Type C20 Inlet
Type C20 Inlet
Type C20 Inlet
Type C20 Inlet
L5-30P
L5-30P
Power Cord
Power cables must be ordered separately.
10/3AWG 10’
10/3AWG 10’
Ethernet Control
NO
YES
NO
YES
NO
YES
YES
YES
Serial Control (RS232)
YES
YES
YES
YES
YES
YES
YES
YES