Fujitsu S26361-F2735-L130 Manual De Usuario
Product Facts
⏐ Issue: March 25, 2008 ⏐ Product: PRIMERGY rack systems Design guide
Page 7 / 89
2 Installation
dimensions
The dimension that is guaranteed as reliable by all rack manufacturers is the installation width of 19” (Rw > 450 mm). So that
this dimension can be respected in all cases, the housing width Hw is limited to a maximum of 448 mm for FSC products.
The height dimensions are guidelines for ensuring smooth installation or insertion. They are always relative to the start or the
end of a height unit U (1 U = 44.45 mm).
Assuming a space of one U, the following tolerance dimensions exist:
measuring point
L
M
R
90°
90°
450.5 mm +1/-0
465.5 mm +2.2/-1
UM
for all front plates =<1U
UL
LL
LM
LR
UR
0.5mm
plate 1U
plate 1U
plate 1U
1U = 44.45mm
1mm
Distance between plate and unit (U)
Distance between plates
LOWER SLOT
UPPER SLOT