Unpacking and Installing the Cisco ONS 15216 Five-Component Bay Assembly (15216-TERM-BAY)
78-15972-01
GMT-TPA Fuse and Alarm Panel
Warning
If you use redundant power leads to power the ONS 15216, disconnecting one lead will not remove
power from the node.
power from the node.
Caution
Always use the supplied ESD wristband when working with a powered ONS 15216. Plug the wristband
cable into the ESD jack located on the lower-right outside edge of the shelf assembly.
cable into the ESD jack located on the lower-right outside edge of the shelf assembly.
Central Office Ground to Bay Wire Ground
Connect the CO ground to the bay wire ground according to local site practice.
Note
The bay assembly ground must be attached to the common central office (CO) ground via an H TAP
compression connector.
compression connector.
FAP Output and Input Power
Route and connect output and input power according to local site practice.
through
show output and input lugs and wiring and
and
list lug wiring positions.
Note
CO power from the BDFB to the bay assembly must be a direct feed from a single breaker (one breaker
for return, and one breaker for -48VDC) at the BDFB to the input connection of the bay assembly. The
size or gauge of the power wire feed must be calculated by the distance from the BDFB to the FAP.
for return, and one breaker for -48VDC) at the BDFB to the input connection of the bay assembly. The
size or gauge of the power wire feed must be calculated by the distance from the BDFB to the FAP.