Cisco Cisco ONS 15454 M6 Multiservice Transport Platform (MSTP)

Descargar
Página de 23
Revised: November 23, 2016, OL-25030-01
Introduction
This document provides information about Cisco NCS users and node timing.
With references provided to configuration guides, see:
Note
• For software releases 9.3 to 9.8, the Cisco ONS 15454 DWDM Configuration Guide
• For software release 10.0 and later, an appropriate guide from one of these three:
◦Cisco ONS 15454 DWDM Control Card and Node Configuration Guide
◦Cisco ONS 15454 DWDM Line Card Configuration Guide
◦Cisco ONS 15454 DWDM Network Configuration Guide
The document contains the topics mentioned below.
Node Timing Parameters
SONET timing parameters must be set for each Cisco NCS shelf. The NCS independently accepts its timing reference from the
internal ST3 clock of the control card.
The BITS connection on Cisco NCS 2006 shelf is through the external connection unit (ECU) and is through the power module on
Cisco NCS 2002 shelf.
In typical NCS networks:
• One node is set to external. The external node derives its timing from a BITS source wired to the BITS backplane pins. The
BITS source, in turn, derives its timing from a primary reference source (PRS) such as a Stratum 1 clock or global positioning
satellite (GPS) signal.
• The other nodes are set to line. The line nodes derive timing from the externally timed node through the OC-N/STM-N trunk
(span) cards. The DWDM node normally derives timing from the line using the OSCM or OSC-CSM card that are inside an
OC-3/STM-1 channel.
You can set three timing references for each NCS. The first two references are typically two BITS-level sources, or two line-level
sources optically connected to a node with a BITS source. The third reference is usually assigned to the internal clock provided on
every NCS control cards. However, if you assign all three references to other timing sources, the internal clock is always available
as a backup timing reference. The internal clock is a Stratum 3 (ST3), so if an NCS node becomes isolated, timing is maintained at
the ST3 level.
The CTC Maintenance > Timing > Report tab show current timing information for an NCS, including the timing mode, clock state
and status, switch type, and reference data.
Mixed timing allows you to select both external and line timing sources. However, Cisco does not
recommend its use because it can create timing loops. Use this mode with caution.
Caution
2