Intel® Server System SR1695GPRX TPS 
Power Sub-System 
Revision 1.5 
 
 
27 
Intel order number: G11332-006 
3.6.1 
I2C Data and Clock 
I2C data and clock signals shall be used to communicate power supply status with end 
use system. 
3.6.2 
PSU Address Lines A0 
Address pins A0 is used by end use system to allocate unit address to a power supply in 
particular slot position. 
For redundant systems there are two signals to set the address location of the power supply 
once it is installed in the system; Address0 and Address1. For non-redundant systems the 
power supply device address locations should align with the Address0/Address1 location of 0/0. 
Table 33. PSU addressing  
PDB addressing Address0 
Power supply PMBus
TM
 device 
B0h 
B2h 
 
Note: Non-redundant power supplies will use the 0 address locations. 
3.6.3 IPMI 
FRU 
Addressing 
If the power supply has a FRU (field replaceable unit) serial EEPROM; it shall be located at the 
following addresses. 
Table 34. PSU FRU addressing  
System addressing Address0 
FRU device addresses 
2
 A0h/A1h 
1
 A2h/A3h 
Notes: 
Non-redundant power supplies will use the 0 address location. 
The addressing method uses the 7 MSB bits to set the address and the LSB to define whether a device is 
reading or writing. The addresses defined above use 8 bits including the read/write bit.