Intel® Server System SR1695GPRX TPS
Power Sub-System
Revision 1.5
27
Intel order number: G11332-006
3.6.1
I2C Data and Clock
I2C data and clock signals shall be used to communicate power supply status with end
use system.
use system.
3.6.2
PSU Address Lines A0
Address pins A0 is used by end use system to allocate unit address to a power supply in
particular slot position.
particular slot position.
For redundant systems there are two signals to set the address location of the power supply
once it is installed in the system; Address0 and Address1. For non-redundant systems the
power supply device address locations should align with the Address0/Address1 location of 0/0.
once it is installed in the system; Address0 and Address1. For non-redundant systems the
power supply device address locations should align with the Address0/Address1 location of 0/0.
Table 33. PSU addressing
PDB addressing Address0
0
1
Power supply PMBus
TM
device
B0h
B2h
Note: Non-redundant power supplies will use the 0 address locations.
3.6.3 IPMI
FRU
Addressing
If the power supply has a FRU (field replaceable unit) serial EEPROM; it shall be located at the
following addresses.
following addresses.
Table 34. PSU FRU addressing
System addressing Address0
0
1
FRU device addresses
2
A0h/A1h
1
A2h/A3h
Notes:
1
Non-redundant power supplies will use the 0 address location.
2
The addressing method uses the 7 MSB bits to set the address and the LSB to define whether a device is
reading or writing. The addresses defined above use 8 bits including the read/write bit.
reading or writing. The addresses defined above use 8 bits including the read/write bit.