Samsung AR30JVFUCWKNMG Manual De Usuario

Descargar
Página de 49
English-37
ENGLISH
Cutting or extending the pipe
Indoor outlet pipe
Connecting pipe
Flare nut
Wall
Indoor unit
Drain hose
The drain hose must  NOT 
slant upwards. 
The end of the drain hose must NOT 
be placed under water.
The drain hose must not 
be bent.
Keep a clearance of at least 
5cm between the end of the 
drain hose and the ground.
5cm
less
Do not place the end of the 
drain hose in a hollow.
Ditch
5.  Check if you flared the pipe correctly (see examples of incorrectly flared pipes below).
6.  Align the pipes to connect them easily. Tighten the flare nuts first with your hands, and then with a torque wrench, 
applying the following torque:
7.  For further details on how to connect to the outdoor unit and purge the air, refer to page 39~41.
Correct
Uneven 
Thickness
Cracked
Damaged 
Surface
Inclined
•  Excessive torque can be cause of gas leakage. If extending pipe by welding/brazing please ensure nitrogen is
     used during welding/brazing process. The joint must be accessible and serviceable.
•   Tighten the flare nut with torque wrench according to specified method. 
If the flare nut is over-tightened, the flare may break and cause refrigerant gas leakage.
When installing the drain hose for the indoor unit, check if condensation draining is adequate.   
When passing the drain hose through the 65-mm hole drilled in the wall, check the followings:
Installing and connecting the drain hose of the indoor unit
Outer Diameter
Torque
N•m
kgf•cm
ø6.35 mm
14~18
140~180
ø9.52 mm
34~42
350~430
ø12.70 mm
49~61
500~620
ø15.88 mm
68~82
690~830
MAX4 AR30JV&JS_IB&IM_DB68-04541A_EN.indd   37
2014/9/26   16:38:59