HP bl30p Manual De Usuario

Descargar
Página de 38
ProLiant BL p-Class Server Blade Enclosure and Interconnects
ProLiant BL p-Class
Server Blade Enclosure
6U (10.5-inch), 19-inch wide
Holds up to:
Eight (8) ProLiant BL20p series server blades
Sixteen (16) ProLiant BL30p series server blades (BL30p blade sleeves required)
Two (2) ProLiant BL40p series server blades
A combination of the above
NOTE: ProLiant BL p-Class server blade enclosures with enhanced backplane components are required to support
BL30p server blades.
NOTE: Server Blade Enclosure Upgrade Kit (354100-B21) contains enhanced backplane components and enables a
field upgrade of a blade enclosure to support BL30p series blades and provide a single, physical iLO port for the
enclosure.
Two (2) outside bays for interconnects (Patch Panel, Patch Panel 2, GbE Interconnect Switch, or GbE2 Interconnect
Switch)
Server blade management module on the rear of the server blade enclosure is hot-plug, has a centralized 10/100T
iLO port for all installed blades, reports events of all installed blades and provides asset and inventory information via
SNMP.
ProLiant BL p-Class
Power Requirements
Redundant 208V 30amp 3-phase 4 wire, NA
Redundant 380 - 415V 20A 3-phase 5 wire, Intl
NOTE: 3 phase power highly recommended for BL30p deployments.
Redundant 200V - 240V AC, 30 amp single-phase for NA and International
Redundant -48VDC ± 10%
QuickSpecs
HP ProLiant BL30p Server Blade
Standard Features (Server Blade Enclosure and Interconnects)
DA - 11958   North America — Version 6 — September 24, 2004
Page 10