HP dl385 Manual De Usuario

Descargar
Página de 112
 
Hardware options installation 49 
 
WARNING:
  To reduce the risk of electric shock, fire, and damage to the equipment, this 
product must be installed in accordance with the following guidelines: 
 
This power supply is intended only for installation in HP servers located in a restricted 
access location. 
 
This power supply is not intended for direct connection to the DC supply branch circuit. It 
should only be connected to a power distribution unit (PDU) that provides an independent 
overcurrent-protected output for each DC power supply. Each output overcurrent-protected 
device in the PDU must be suitable for interrupting fault current available from the DC 
power source and must be rated no more than 50A. 
 
This power supply is designed to be connected only to a DC power source that can be 
classified as SELV or TNV, in accordance with applicable national requirements for 
Information Technology Equipment and Telecommunications Equipment. Generally, these 
requirements are based on the International Standard for Information Technology 
Equipment, IEC 60950, and/or the European Telecommunication Standard ETS 300 132-
2. The DC source is to have one pole (Neutral/Return) reliably connected to earth ground 
in accordance with local/regional electric codes and/or regulations. 
 
The green/yellow lead of the power cable assembly must be connected to a suitable 
ground/earth terminal. This terminal must be connected to a suitable building ground/earth 
terminal in accordance with local/regional electric codes/regulations. Do not rely on the 
rack or cabinet chassis to provide adequate ground/earth continuity. 
  
 
  
 
WARNING:
  To reduce the risk of personal injury or damage to the equipment, the installation 
of power supplies should be performed only by individuals who are qualified in servicing 
server equipment and trained to deal with products capable of producing hazardous energy 
levels. 
  
  
 
WARNING:
  To reduce the risk of personal injury from hot surfaces, observe the thermal labels 
on each power supply or module. 
  
  
 
WARNING:
  To reduce the risk of injury from electric shock hazards, do not open power 
supplies. Refer all maintenance, upgrades, and servicing to qualified personnel. 
  
  
 
CAUTION:
  Do not run the server with one AC power supply and one DC power supply 
installed. 
  
  
 
CAUTION:
  Electrostatic discharge (ESD) can damage electronic components. Be sure that you 
are properly grounded (earthed) before beginning any installation procedure. 
  
To install the component: