3.2.14 Surge Protector Installation
Overview
A massive electrical surge can be caused if lightning strikes a telephone cable 10 m above ground, or if a 
telephone line comes into contact with a power line. A surge protector is a device that is connected to a trunk 
to prevent potentially dangerous electrical surges from entering the building via the trunk and damaging the 
PBX and connected equipment.
To protect the system from electrical surges, we strongly recommend connecting the system to a surge 
protector that meets the following specifications:
Surge arrestor type: 3-electrode arrestor
DC spark-over voltage: 230 V
Maximum peak current: at least 10 kA
Additionally, proper earthing is very important for the protection of the system (refer to "3.2.5 Frame Earth 
Connection
").
Many countries/areas have regulations requiring surge protection. Be sure to comply with all applicable 
laws, regulations, and guidelines.
Installation
Trunk
Trunk
Trunk
Earth
Surge 
Protector
Extn.
Extn.
Extn.: Extension line
SLT
PT
PT-interface CS
CS
PBX
Frame 
Earth
Terminal 