Because of the external dimensions of the 4200FA UPS and the way the outer panels are to be 
removed; only a minimum amount of space around the unit is required for ventilation and 
maintenance access.  Figure 3.1 shows the minimum clearances required for proper UPS 
installation. 
 
3.1  
Installation 
Precautions 
1)  Install the UPS in a stable, level, and upright position that is free of vibration. 
2)  Install the UPS in a well ventilated location with the required allowances for ventilation 
and servicing as shown in figure 3.1. 
3)  Install the UPS where the ambient 
temperature is within the correct 
operating range (see the UPS 
Specifications in section 5). Verify that 
the ventilation and air conditioning 
system at the site is capable of 
removing the heat generated by the 
UPS unit (see Section, 5 Specifications, 
"Environment"). Ambient temperature 
range for operating the UPS is 32 – 
104 °F (0 – 40 °C); 77 °F (25 °C) is the 
recommended operating temperature 
for maximum battery life.
 
4)  Do not install the UPS in a location that 
is subject to high humidity. 
5)  Do not allow the UPS to be exposed to 
direct sunlight. 
6)  Do not install the UPS in areas that are 
subject to contamination such as high 
levels of airborne dust, metal particles, 
or flammable gasses. 
7)  Avoid installation near sources of 
electrical noise and always ensure that 
the earth ground is intact to prevent 
electrical shock
 and help prevent 
electrical noise. 
8)  Do not install the UPS in an area that 
may expose the UPS to water or that 
may allow any foreign matter to get 
inside. 
9)  This UPS generates and radiates radio-
frequency energy during operation. 
There is no guarantee that the UPS will 
not influence some sensitive devices 
that are operating close by. If such 
interference is experienced, the UPS 
should be installed farther away from 
the affected equipment and/or powered 
from a different source than the affected 
equipment. 
10) The user should provide output over 
current protection for hardwired UPS 
versions. See Safety Instructions on 
page 9 for the correct device rating. 
Figure 3.1 
FRONT 
28” (700 mm) 
REAR 
0” (0mm) 
LEFT 
0” (0mm
TOP 
22” (550 mm) 
RIGH
0” (0mm
4200 FA User’s Manual   
11