Recommended Wire Size and Tightening Torque for UPS Input/Output Terminals 
 
Minimum/Maximum Wire Size and Tightening Torque 
of UPS Input and Output Terminals
 
Main Input & 
Bypass Input 
AWG 
(H1 – H3, 
BYP1, BYP2, BYP3) 
AWG 
(N, BYPN) 
Tightening Torque 
(in-lbs.) 
208 VAC 
300 MCM to 500 MCM 
400 MCM to 500 MCM 
375 
380, 400, 415 VAC 
2/0 AWG to 500 MCM 
400 MCM to 500 MCM 
375 
480 VAC 
1/0 AWG to 500 MCM 
400 MCM to 500 MCM 
375 
600 VAC 
1/0 AWG to 500 MCM 
400 MCM to 500 MCM 
375 
 
Output 
AWG 
(L1, L2, L3) 
AWG 
(OUTN) 
Tightening Torque 
(in-lbs.) 
208 V/120 VAC 
300 MCM to 500 MCM 
400 MCM to 500 MCM 
375 
 
Battery Circuit 
AWG 
(POS, NEG) 
Tightening Torque 
(in-lbs.) 
288 VDC Nominal 
400 MCM to 600 MCM 
500 
 
Input/Output 
Ground 
AWG 
(GND) 
Tightening Torque 
(in-lbs.) 
 
2 AWG minimum  (see note 1) 
(see note 2) 
     All wire sizes are per NEC 
     Use copper wiring with at least 90°C rated insulation 
     Neutral Conductors are rated @ 1.73 or 200% of phase conductors, per NEC 
     Note 1: Use a UL listed lug suitable for the wire size used. 
     Note 2: Use tightening torque recommended by manufacturer of lug used. 