TOSHIBA 
 
6.9.4 
Line-4 System Messages 
Line-4 messages reflect the UPS operating conditions. Warning messages will be displayed 
when an abnormal operating condition occurs. The following table shows the allowable Line-4 
messages. 
 
LINE-4 MESSAGES 
Displayed Message 
Meaning 
Displayed when input Phase rotation has been wired 
in a counter clockwise rotation. 
PHEI 
Displayed when input and output frequencies are not 
synchronized.  (abnormal) 
I/O NOT SYNCHRONIZE 
Displayed when auto-transfer to bypass is active (i.e. 
current limit reached).  (abnormal) 
* AUTOTRANSFER * 
Displayed when battery voltage is low (abnormal) or 
the UPS batteries have failed self-diagnostic test.  
(abnormal) 
* BATTERY LOW * 
Displayed when UPS has tripped due to an overload 
condition.  (abnormal) 
* UPS OL: REDUCE LOAD * 
Displayed when the UPS has an internal failure. 
(abnormal) 
* DCOC * 
Displayed when the UPS has an internal DC bus 
over-voltage. (abnormal) 
* DCOV * 
Displayed when the UPS has an internal DC bus 
unbalance referenced to Neutral. (abnormal) 
* DCUB * 
Displayed when UPS has tripped due to an overload 
condition.  (abnormal) 
* UPS OL * 
Displayed when inverter output over-voltage has 
occurred. (abnormal) 
* INOV * 
Displayed when inverter output under-voltage has 
occurred. (abnormal) 
* INUV * 
Displayed when the optional battery over-temp 
sensor has annunciated, or if the external battery 
disconnect is open. (Verify TB3-5,6) 
* BATTOH *OR MCCB-B OPEN 
Displayed when none of the above abnormal 
conditions are present. (normal) 
* UPS OK * 
Displayed when none of the above abnormal 
conditions are present and the UPS is in battery 
discharge mode. (normal backup) 
* DISCHARGE CURR=###% * 
Displayed when key switch position is changed and 
frequency is not synchronized. (abnormal) 
* TRANSFER INHIBITED * 
Displayed when an emergency (EPO) signal is 
received. 
* EMERGENCY OFF * 
Displayed when UPS has normally shutdown. 
* UPS OUTPUT DISABLED * 
Displayed when a fault or faults have occurred. 
(abnormal) 
* FAULT(S) DETECTED * 
 Note: 
1) 
Line-4 will be blank when the BATT key is pressed during battery backup mode 
with normal battery voltage. 
 
2) 
The # symbol signifies numerical values or other information supplied by the UPS. 
 
4200 FA User’s Manual   