Toshiba 4200FA Manual De Usuario

Descargar
Página de 66
TOSHIBA 
 
36 
Operating the UPS 
5.7 
Operating the UPS 
 
5.7.1 
AC Input Mode (Normal Operation) 
The following illustration shows circuit power flow when the UPS is operating normally in the 
AC Input Mode. The rectifier includes a boost chopper circuit that converts the AC input power 
into DC power. The boost chopper circuit maintains a constant voltage with current limiting 
abilities for charging the batteries. The rectifier supplies a DC voltage of the proper level to the 
inverter section. The inverter section generates a high quality sine wave output voltage. The 
batteries are maintained in a constantly charged state when the UPS is in the “Normal 
Operation Mode.” 
 
 
Power flow in AC Input Mode 
5.7.2 Bypass 
Mode 
If the UPS unit is severely overloaded or develops an internal fault, power flow is automatically 
switched from the main circuit to the Bypass circuit.  Power flow through the bypass is shown 
in the following illustration. This changeover occurs automatically in less than 4 milliseconds in 
phase (Make-Before-Break). If the power flow is transferred to the Bypass circuit because of 
an overload and that overload condition ends within a specified period of time, then the power 
flow will "re-transfer" to the AC Input Mode (Normal Operation) automatically. If the power 
flow is transferred to the Bypass circuit due to a fault condition, then the power flow 
must be transferred manually from the UPS's Bypass circuit back to the Inverter circuit 
after repairing the fault
 (see "Start-up Procedure"). If the power flow is transferred to the 
Bypass circuit due to an overload condition, then the power flow will automatically 
transfer from the UPS's Bypass circuit back to the Inverter circuit after removing the 
overload
 
(see "Overload Operation").  
 
 
 
Power flow in Bypass mode 
5.7.2.1  Bypass Mode for Optional Alternate Input Models 
 
Input  
Power 
Isolation 
Transformer 
Model 
MCCB 
Converter Inverter 
Chopper 
Batteries 
  Bypass 
  MBS 
Output 
Power 
Input  
Power 
Isolation 
Transformer 
Model 
  MCCB
 MBS 
 Bypass
Converter Inverter 
Output 
Power 
Chopper 
Batteries