5.10 Battery 
Recharging 
The illustration below shows a graphical representation of the UPS battery recharge process 
after a full discharge. 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
The recharge process usually consists of three steps. During the first step, the charging current 
is maintained at approximately 4.0 amperes for the 15/25/30/33kVA and approximately 11.5 
amperes for the 50 kVA. This current is the maximum value that can be used to charge the 
batteries (for minimal recharge time) while assuring safety and long battery life. In the second 
step, constant-voltage control starts and current gradually decreases as the batteries charge to 
their normal fully charged state.  In the third step, a slight "trickle" current continues to flow into 
the batteries to keep them fully charged and "floating" at the normal DC Voltage level. A full 
recharge usually requires approximately 24-72 hours (90% recharge in 10 hours) after a 
complete discharge.  
 
The following chart shows the rated maximum and minimum battery voltages, and the charge 
current for each of the sizes while the unit is maintained in a 75°F (24
° C) ambient. 
 
Rated Battery Voltages 
15/25/30/33  
50kVA 
Model 
Internal 
Battery 
Internal 
Transformer 
Internal 
Battery 
Internal 
Transformer 
V float 
324.0 VDC 
324.0 VDC 
324.0 VDC 
V min 
252 VDC 
252 VDC 
252 VDC 
I charge 
4.0 A 
10.0 A 
11.5 Amps