6.0  UPS Protection System 
6.1 
System Protection Features 
The preceding one-line schematic illustrates the electrical locations of the protection devices 
on all UPS models. 
 
 
 
 
  
6.2 
System Protection Functions 
The following chart shows the built-in UPS fault protection functions on all models. 
 
Built-in UPS Fault Protection Functions 
Protection Item 
Inverter Over-voltage 
(IVOV) 
Inverter Under-voltage 
(IVUV) 
UPS Overload 
LCD Message 
INVERTER 
OVERVOLTAGE 
INVERTER 
UNDERVOLTAGE 
OUTPUT OVERLOAD 
Cause 
Control Malfunction; Feedback Error 
Overload or short circuit at the load. 
Operation Mode 
after Fault 
Bypass Operation; Chopper and Inverter Stopped 
Inverter Overload: Transfer to bypass; Inverter 
stopped. 
Bypass Overload: Inverter, Chopper, and Bypass 
stopped. 
Audible Alarm 
Yes: See Audible Alarm Functions 
Visible Alarm 
Red Fault Lamp “on” 
Inverter OL: No Fault Lamp 
Bypass OL: Fault Lamp “on” 
Relay Contact 
Alarm 
Fault Relay closed; Bypass Relay closed 
Inverter OL: Bypass Relay closed 
Bypass OL: Bypass Relay open and Fault relay 
closed 
Auto-Retransfer 
No 
Inverter OL: Yes, if bypass ok 
Bypass OL: No 
 
Protection Item 
Low Battery Voltage 
(Level-1) 
Low Battery Voltage 
(Level-2) 
Inverter Output Current Limit 
LCD Message 
Line-4 will read 
“BATTERY LOW” 
DC UNDERVOLTAGE 
OUTPUT OVERLOAD 
Cause 
Battery Discharge 
Battery Shutdown Level 
reached 
Load Inrush current 
Operation Mode 
after Fault 
Battery Discharge 
Shutdown:  
No Output 
If Bypass ok, transfer to bypass; if not, current-limit 
mode 
Audible Alarm 
Yes: See Audible Alarm Functions 
Visible Alarm 
Battery Lamp Flickers 
NO 
NO 
Relay Contact 
Alarm 
Low Battery Relay 
closed 
Bypass Relay closed 
Auto-Retransfer 
No 
Yes, if bypass ok 
Input 
Power 
Isolation 
Transformer 
Model 
 MCCB 
  Converter 
Inverter 
Output 
Power 
  Bypass 
  MBS 
Chopper 
Batteries 
Input 
Abnormal 
Overcurrent 
Low Battery 
Overheat 
Overload 
Over-voltage/ 
Under-voltage