8.3 Parameter initial settings list 
 
Unless otherwise specified, the default values for each parameter shown below are set when shipped from 
the factory: 
Parameter names 
Default value 
Excitation frequency 
(*1) 
Flow direction 
NORMAL 
Display 1 
gal/min 
Display 2 
COUNT B 
Display digit setting 
  (for Display 1 and Display 2) 
1/1000 
Custom coefficient 
1.0 
Custom unit 
“ CUSTOM”(Head of character string is blank ) 
Range type 
Single 
Range 1   
300 gal/min 
Ranges 2 to 4 
0 gal/min 
Hysteresis 3.0 
Damping constant 
5.0 s 
Rate-of-change limit 
0.0 % 
Control limit time 
0.0 s 
Low cutoff 
1.0 % 
Display low cutoff 
LINEAR 
Manual zero 
0.0 % 
4
−20mADC alarm output 
4mA 
Output low limit setting 
4mA 
Digital output 1 
NO USE 
Digital output 2   
NO USE 
DO1/DO2 active status   
NormOPEN 
Digital input   
NO USE 
DI detective level 
H LEVEL 
Count rate 
100 gal 
Pulse width setting mode 
AUTO 
Pulse width 
5 ms 
Preset count 
00000000 
Preset function 
HOLD 
High alarm On/Off 
OFF 
High alarm value 
0.0 % 
Low alarm On/Off 
OFF 
Low alarm value 
0.0 % 
High-High alarm On/Off 
OFF 
High-High alarm value 
0.0 % 
Low-Low alarm On/Off 
OFF 
Low-Low alarm value 
0.0 % 
Empty pipe alarm 
NORMAL 
Self-diagnosis On/Off 
ON 
Converter alarm 
CONV ONLY 
Fixed value output 
OFF 
Fixed value current 
4mA 
Fixed value pulse 
0 pps 
Password 000 
LCD density adjustment 
Switch position setting 
BOTTOM 
*1: See the setting values for each meter size in the table below.