Multiple range high/low limit alarm output 
 
 
Note 1: Range changes to Small range when range select signal is H level, and to Large range in L 
level. 
Note 2: High-high/low-low limit alarm is activated when Small range is selected. High/low limit 
alarm is not output to display. 
High/low limit alarm is activated when Large range is selected. High-high/low-low 
limit alarm is not output to display. 
Note 3: Alarm output state is the same state to which digital output 1 or 2 is set. When converter 
power is OFF, contact output is OPEN. 
Note 4: Each alarm set value % is the percent set to the first range. 
Note 5: Hysteresis of each alarm is 2.5 % for the first range. 
 
Example 
When Large range and Small range are set as below: 
Large range (Range 1):   
1000 m
3
/h 
Small range (Range 2): 
500 m
3
/h 
And you want to set alarm values as below: 
Large range alarm set values 
High limit value: 
800 m
3
/h 
Low limit value: 
600 m
3
/h 
Small range alarm set values 
High-high limit value:  400 m
3
/h 
Low-low limit value:  300 m
3
/h 
Set the alarm set values as below: 
High limit value: 
80 % (800 m
3
/h
÷1000 m
3
/h=0.8) 
Low limit value: 
60 % (600 m
3
/h
÷1000 m
3
/h=0.6) 
High-high limit value:  40 % (400 m
3
/h
÷1000 m
3
/h=0.4)  See Note4. 
Low-low limit value:  30 % (300 m
3
/h
÷1000 m
3
/h=0.3)  See Note4 
 
 
 
 
Low-low limit
 
High-high limit
 
Low limit
 
Flow rate
 
High limit
 
Small range (Range 2)
Large range (Range 1) 
Alarm output ON
 
Alarm output ON
Alarm output ON
Alarm output ON
Alarm output ON
 
DI range select signal 
Multiple range
 
High limit alarm output
 
DO1
Multiple range 
Low limit alarm output
 
DO2
 
Time