 132 − 
 
6 F 8 A 0 9 3 4  
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
Figure 11.2    Connections to the Converter Unit 
 
11.2 Procedure for Communications with HHT 
 
This section describes the HHT basic operation procedure for communications between the flowmeter 
and HHT. For details, refer to the HHT instruction manual. 
* The following procedure makes a commercially available PDA (OS: Windows Mobile) serve as a 
HHT. 
Procedure Operation 
Prepare a hand-held terminal (1) 
Install the AF900 application software to a commercially available PDA (OS: 
Windows Mobile) main unit. Then insert the serial interface card supplied with 
AF900 to the card slot of the PDA. 
Prepare a hand-held terminal (2) 
Connect the HART interface cable and serial interface card supplied with 
AF900 to each other. 
Connect 
Connect the alligator clip at the head of the HART interface cable to the current 
output line of the converter via a load resistor. 
Start 
Turn on the power supply of the PDA to start the AF900 application software. 
Preliminary communication 
Execute [sensor communication]. The model of the connected sensor product 
is automatically identified and the converter menu screen appears. 
Check/change data 
Press the relevant parameter button and check/change data. 
Exit the communication 
When all operations are complete, press the [Exist Application] in the top 
screen to turn off the power supply of the PDA. 
 
HHT connection cable and clips 
Converter terminal block 
HHT