5.2 External Device Connections and Grounding 
The terminal board connections of LF516/LF546 Flowmeter are shown in Figure 5.1. Proceed with wiring 
as described in Section 5.4, “Wiring Procedure.” 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
Figure 5.1    External Wiring Schematic Diagram 
* Use a heavy copper braid or wire (cross-sectional area 5.5 mm
2
 minimum) to ground the terminal 
and make it as short as possible as shown in Figure 5.1 for grounding. 
Also,  Avoid a common ground where earth current may flow. (An independent ground is 
preferable.) 
* The converter has no power switch. Install the power switch at the system side. Be sure to use a 
double-pole/single-throw (both disconnection) wiring breaker.
Power supply 
Wiring breaker 
(double-pole/single-throw) 
Output signal cable 
(CVV-S) 
Current output 
(4-20mAdc) 
or PROFIBUS 
NOTE: 
To avoid 2-point grounding, 
ground the shield of the output 
cable basically at the receiving 
side. 
Digital output 1 
Common for DI/DO 
(100 ohm or less 
ground resistance) 
Digital output 2 
Digital input 
(20 to 30 Vdc) 
Power cable (CVV) 
* For a 2-core cable, L1 and 
L2 only. 
IV wire 
5.5mm
2
 or more 
Ground terminal 
(100 ohm or less 
ground resistance) 
Converter unit 
(100 ohm or less ground 
resistance) 
NOTE: 
• When 3-core power cabel is used, do 
not ground from the    external 
grounding terminal.(Perform grouding 
at the receving side only). 
• Only when a 2-core power cable is 
used, perform grounding from the 
external grounding terminal. 
[Instrumentation panel: Customer] 
(Receiving side)