 71 − 
 
6 F 8 A 0 9 3 4  
 
Switch operation 
Display example 
Description 
STEP3 
 
 
 
R HYS 
 
      0
5
.0 
 
         % 
 
 
 
Push              to  move  the  cursor  to  the 
desired digit and push      to change the 
number of the digit. 
 
STEP4(=END) 
 
 
 
R HYS 
 
      05.0 
 
         % 
SET OK?
 
 
 
When you push      , a message appears 
to confirm whether the setting is OK or not. 
If OK, push       . If you want to redo the 
setting, push      . 
 
Pushing      cancels the setting operation 
and exits the setting screen. 
 
Note: If you try to set a value exceeding 25.0%, HIGH OVER SPEC error appears and the 
value returns to the previous value. Set a value once again. 
 
8.2.10 Damping Constant 
 
The damping constant is used to moderate output fluctuations. (The larger the damping constant, the more 
the output is averaged. But the response to an input change will be slower.) The damping constant can be 
set as follows: 
The damping constant is set for 0.0 sec, 0.5 sec and 1 to 200 sec (in increments of 1 second) 
Note:  0.0 sec setting will work as equal to 0.1 sec damping constant. 
Set 1 sec or more for normal operation. 
If you set a value exceeding 200s, it is forcibly changed to 200s before data is written. 
 
Proceed as follows to check or change the damping constant. 
Shown below is an example of changing the damping constant from 5.0s to 10s. 
 
 
Switch operation 
Display example 
Description 
 
D:FILTER 
1 DAMPING
 
2 LIM RATE 
3 LIM TIME 
4 EXIT 
 
 
Select "DAMPING" from the setting item 
selection menu.
 
 
 
STEP1 
 
 
 
DAMPING 
 
      05.0 
 
         S 
 
 
 
The currently set damping constant (5.0s in 
this example) appears. 
 
Then push      . 
 
 
N O
O K
ESC 
O K
N O
ESC
ESC 
ESC