8.2.22 Preset Mode 
 
The preset mode determines the function when the totalizer reaches the preset count. 
The present mode can be set from the items shown below. 
 
●Preset mode 
 
  Selection items 
Preset mode 
   HOLD 
 Holds the output value. 
      50ms PLS 
  Outputs a one shot pulse of 50ms width. 
      500ms PLS 
  Outputs a one shot pulse of 500ms width. 
Note: If you set the preset mode to "50ms PLS" or "500ms PLS", you need to set the preset 
count to 1, 2, 5, 25, 125 
×10
n
. (If you set a value that does not meet this condition, the 
preset output timing may be shifted when the totalizer overflows. 
 
You can check or change the preset mode as described below. 
 
The following is an example to change the present mode from Output condition hold (HOLD) 
to One-shot pulse output with pulse width of 50ms (50ms PLS). 
Switch operation 
Display example 
Description 
 
K:PRESET C 
1 PRST VAL
 
2 OUT MODE
 
3 EXIT 
 
 
 
 
Select "OUT MODE" from the setting item 
selection menu. 
STEP1 
 
 
 
OUT MODE 
 
HOLD 
 
 
 
 
The current setting (HOLD in this example) 
appears. 
 
Then push              . 
 
* Pushing       returns you to the menu 
screen. 
 
ESC 
ESC