Operating the UPS 
Display Panel Layout 
 
ON LINE (green lamp) 
Lights green when the UPS’s inverter is 
supplying power to the load. 
 
AC INPUT (green lamp) 
Lights green when normal AC input power 
is being supplied to the UPS unit. 
 
WARNING/FAULT (red lamp) 
Lights red when the UPS unit is 
experiencing an abnormal condition. 
 
BATTERY (red lamp) 
Lights red to indicate that a condition exists 
that is affecting the batteries. 
 
Starting the UPS System 
Once the modules have been connected as shown in the preceding 
section (UPS Connections, page 10) the UPS system is ready to be 
started.  There are two ways to start the system:  from AC input 
power (if present) or from batteries.  If not already done, switch the 
input breaker on (figure 1, page 9).   If the “AC Input” LED is lit, 
proceed on to “Starting when AC power is available”.  If the LED is 
not lit, there is no AC power available.  If the unit is to be started 
when AC power is not available proceed to “Starting on DC power.” 
 
Starting When AC Power is Available 
If the system is being started with AC input power the system is 
started by switching the RUN/STOP switch to the RUN position 
(RUN = I, STOP = 0).  When the RUN/STOP switch is in the RUN 
position both the “AC Input” and the “On Line” LEDs should be lit.  
When the unit is started with AC input power it is advisable to allow 
time for the batteries to fully charge before any load is connected 
(see “Battery Recharge Time”, page 15). 
 
 
Startup on 
Battery 
Button 
Function  
Control 
Button