Appendix B:  Fan Speed Control 
The fans in the 1700 Series will operate at any of four different speeds 
depending on the environment and system conditions.  In the first stage 
the fans are off.  As the load and or the temperature increase the fans 
will subsequently go to low, medium or high speed as required. 
 
 
The temperature reference given on the graph above refers to the 
temperature inside the UPS.  There will typically be a 5°C difference 
between the internal and external temperature.  The 10% hysteresis 
shown is to ensure that the unit will not oscillate between fan speeds.  
When the output power reaches a level that requires the fan speed to 
increase the load will have to be reduced 10% below that level before the 
fan speed will return to the lower speed.