SMC Networks sunny mini central smc 6000a Manual De Usuario

Descargar
Página de 96
Technical Data 
SMA 
Technologie AG
Page 82
SMC50A_60A-IEN073320
Installation Guide
14.4 Sunny Mini Central Operating Parameters
14.4.1 Explanation of the Operating Parameters
Unauthorized changes to the operating parameters may result in:
injury or accidents as a result of changing the internal safety
specifications of the Sunny Mini Central,
voiding the Sunny Mini Central operating approval certificate,
voiding the Sunny Mini Central warranty.
Never change the parameters of your Sunny Mini Central without express
authorization by the local energy supply company and instructions from
SMA. 
Name
Explanation
ACVtgRPro
Voltage rise protection (only relevant for Germany).
The Sunny Mini Central can feed into the public grid with up to 260
V AC. However, DIN VDE 0126-1-1 stipulates that the average AC
voltage over 10 minutes must not exceed 253 V. If the average over
10 minutes exceeds the threshold value of 253 V, the Sunny Mini
Central disconnects itself from the grid. Once the average over 10
minutes returns to a value of less than 253 V, the Sunny Mini Central
returns to "Working" mode. If voltage rise protection is not required
in the relevant grid area (outside Germany), it can be deactivated
by presetting the LDVtgC parameter. In this event, only the fast cut-
off via the Uac-Max parameter intervenes.
AntiIsland-Ampl Amplification of the anti-islanding process 
(deactivated for GER by setting AntiIsland-Ampl = 0)
AntiIsland-Freq
Repetition rate of the anti-islanding process 
(deactivated for GER by setting AntiIsland-Ampl = 0)
Betriebsart
Operating mode of the Sunny Mini Central:
MPP: Maximum Power Point
Turbine Mode: operating mode for Sunny Mini Central at a
wind turbine
UKonst: constant voltage mode 
(nominal voltage is defined in "Usoll-Konst")
IKonst: operating mode for test purposes
Stopp: disconnection from grid, no operation
Off Grid: operating mode of the Sunny Mini Central 
in a stand-alone grid