Fireplace Requirements
These  heaters  are  designed  to  be  installed  into  an  existing  masonry 
fireplace (built to UBC 37 or ULC S628 standards) or factory built solid 
fuel, wood burning fireplace (listed to UL 127 or ULC S610) only. All 
exhaust gases must be vented outside the structure.  Combustion air 
is drawn from outside the structure. When installing in a factory built 
fireplace, the fireplace grate must be removed and the damper must be 
removed or secured open.
If the factory-built fireplace has no gas access hole(s) provided, an access 
hole of 1-1/2 inches (38 mm) or less may be drilled through the lower 
sides or bottom of the firebox in a proper workmanship like manner. This 
access hole must be plugged with a non-combustible insulation after the 
gas supply line has been installed.  The installer must mechanically attach 
the marking supplied with the gas fireplace insert to the inside of the firebox 
of the fireplace into which the gas fireplace insert is installed.
IMPORTANT: When installing these appliances into a factory 
built fireplace or heat-form, the air flow within and around the 
fireplace shall not be altered by the installation of the insert 
(i.e. DO NOT BLOCK louvers or cooling air inlet or outlet ports, 
circulating air chambers in a steel fireplace liner or metal heat 
circulator). 
•  Must conform with all local, state, and national installation codes. In 
the absence of local codes, the installation must conform with National 
Fuel Gas Code ANSI Z223.1 - latest edition, also known as NFPA 54 
(In Canada, the current CAN/CSA  B149.1 installation code). Refer to 
the National Fuel Gas Code and local zoning and code authorities for 
details on installation requirements.
•  Mobile home installations must conform with the Mobile Home Con-
struction and Safety Standard, Title 24 CFR, Part 3280 (in Canada 
CAN/CSA Z240 MH), or, when such a standard is not applicable, the 
Standard for Mobile Home Installations, ANSI A225.1 - latest edi-
tion.
•  Must be vented directly to the outside in accordance with the latest 
edition of the National Fuel Gas Code and must never be attached to 
a chimney serving a separate solid fuel burning appliance.
•  Has been certified for use with either natural gas or propane.
•  Is not for use with solid fuels.
•  Is approved for sitting rooms and/or bedrooms.
THE SDVI FIREPLACE INSERT
ORIFICE SIZE/ALTITUDE ADJUSTMENT
For altitudes above 2,000 feet (In Canada 4,500 FT/1370 M),the orifice 
should be de-rated by 4% for every 1,000 feet to maintain the proper ratio 
of gas to air. Improper orifice sizing may result in damage and unsafe 
conditions. Changing the orifice should only be done by a qualified service 
technician. Contact your LHP dealer for proper orifice sizes.
WARNING
THIS FIREPLACE HAS BEEN ALTERED TO 
ACCOMMODATE A FIREPLACE INSERT AND 
SHOULD BE INSPECTED BY A QUALIFIED 
PERSON PRIOR TO RE-USE AS A 
CONVENTIONAL FIREPLACE.
SMOKE DETECTORS
Since there are always several potential sources of fire in any home, we 
recommend installing smoke detectors. If possible, install the smoke 
detector in a hallway adjacent to the room (to reduce the possibility of 
occasional false activation from the heat produced by the appliance).  If 
your local code requires a smoke detector be installed within the same 
room, you must follow the requirements of your local code. Check with 
your local building department for requirements in your area.