Contec DIO-4 Manual De Usuario

Descargar
Página de 4
 
 
Ver.1.00
 
  DIO-4/4(FIT)GY 
 
 
3
 
 
 
How to Connect an Interface Connector 
When connecting the Module to an external device, you can 
use the supplied connector plug.     
To wire the Module, strip the sheath about 9 - 10mm from an 
end of the wire and insert the exposed wire into an opening.  
Tighten the screw to fasten the inserted wire.  Applicable 
wires are AWG28 - 16. 
- Applicable wire:
3.81mm pitch, 12-pin type, 8.0A rated current
MC1, 5/12-GF-3.81 [made by Phoenix Contact Corp.]
- Applicable plug:
Front screw type with connector stopper flange
FRONT-MC 1,5/12-STF-3,81 [made by Phoenix Contact Corp.]
Applicable cable: AWG28-16
Turn the screw to fasten the wire.
9 - 10mm
DI-8
Device
ID
COM 0
NC
X
COM1
NC
0
3
1
2
6
5
4
7
4 5 6 7
X
0 1 2 3
0
4
0
4
6
2
5
1
3
7
 
CAUTION  
Removing the connector plug by grasping the cable can 
break the wire. 
Signal Layout on the Interface Connector 
The Module can be connected to an external device using a 
12-pin connector that is provided on the Module face. 
COM 0 --- +/-COM
N.C.
X 0 --- IN 0
X 1 --- IN 1
X 2 --- IN 2
X 3 --- IN 3
Y 0 --- OUT 0
COM 1 --- +COM
COM 2 --- -COM
Y 1 --- OUT 1
Y 2 --- OUT 2
Y 3 --- OUT 3
Input port
plus / minus common
Output port minus common
Digital Input: 4points
Digital Output: 4points
Output port plus common
 
 
 
Input section 
Figure below shows the input equivalent circuit for the interface 
section of this product. 
The signal input section consists of an Optocoupler isolated 
input (compatible with both current sink output and current 
source output).  An external power supply is therefore 
required to drive the input section of this module.    The power 
requirement for the <DIO-4/4(FIT)GY> or <DI-8(FIT)GY> is 
about 8 mA per input channel at 24 VDC (about 4 mA at 12 
VDC). 
Input Circuit 
Vcc
3k
Ω
3k
Ω
External circuit
Module
Optocoupler
Input
pin
Input
pin
+/-
common
Input contact
point
Input contact
point
12V - 24VDC
External
power supply
Optocoupler
 
Example of a Connection to Current Sink Output 
3kΩ
Vcc
Current sink
output
Optocoupler
Input
pin
Minus
common
12V - 24VDC
External
power supply
External circuit
Module
 
Example of a Connection to Current Source Output 
Minus
common
3kΩ
External circuit
Module
Optocoupler
Input
pin
Current
source output
External
power supply
Vcc
 
Output section 
Figure below shows the output circuit for the interface section 
of this product.  The signal output section consists of an 
Optocoupler isolated open collector output (current sink type).   
An external power supply is therefore required to drive the 
output section of this module. 
The maximum output current rating per channel is 150 mA for 
this product (at 12 - 24 VDC) or 50mA for this product (at 36 - 
48 VDC).  A surge voltage protection circuit (zener diode) is 
provided for the output transistors of this module.    When the 
module drives relays, lamps, and other induction loads, 
however, another surge voltage countermeasure should be 
provided on the load side. 
CAUTION  
When the power is turned on, all output will be OFF. 
Output Circuit 
Vcc
Vcc
Plus
common
Minus
common
Output
pin
Output
pin
Optocoupler
External circuit
Module
Load
Load
12V - 48VDC
External
power supply
 
Connection example: 
Using Inputs X0 
+
Input plus common (e.g., connector COM0)
Mo
du
le
 s
id
e
Input pin (e.g., connector X0)
External
power supply
12V - 24VDC
-
 
Interface Connector   
 
External I/O Circuits