Set Up and Calibration Procedures 
Regions of Motor Travel 
62 
  HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual 
Revision 6 
  
 
7/07 
Regions of Motor Travel 
The full span of motor travel can be 90
° or 150° rotation.  The span is divided into 10 regions of motor 
travel as shown in Figure 23 (regions are numbered 0 through 9).  Maintenance statistics are accumulated 
on the total number of motor starts, as well as the total number of motor starts that occur in each region of 
travel.  The statistics can be accessed in the maintenance set up group.  The counts can also be reset to zero 
if desired.  See the Maintenance Set Up Group for more information. The regions of travel are determined 
by the full span motor travel (90
° or 150° rotation).  If the actuator is set up to operate in a smaller range, 
for example between 40% and 80% of full span, the maintenance statistics will show motor starts only in 
regions 4 through 7.  
Degrees of Rotation
Percent of Span
0o                                 30o                                 60o                               90o     
0%                20%                40%                60%                80%             100%
Region of Travel
0          1          2         3          4         5         6          7         8         9
 
 
 
 
De gr ee s of   R ot at io n
Pe rc en t of  S pa n
0o
           30 o
 60 o
            150 o
0%
  20%
      4 0%
   60%
       8 0%
100%
Regio n of Trave l
0          1
2         3
4         5         6
         7         8
        9
 
Figure 23 Regions of Motor Travel