21/88 Operating 
Manual 
SG Series 10, 20, 30 & 40 kVA 
alarm
 
General alarm condition. 
It blinks 
when one or more alarm is activated. The internal buzzer is ON
The  LED  remains lighted (with alarm condition still present) and the 
buzzer stops as the key “mute” has been pressed. 
 
service check
 
LED ON indicates that a regular maintenance service is needed. 
May be reset by a service technician only. 
(See chapter 10 – Maintenance) 
THE  LED IS ON ALSO WHEN THE OUTPUT SWITCH Q1 IS OPEN, 
INDICATING THAT THE INVERTER
 IS IN SERVICE MODE,  NOT 
SUPPLYING THE LOAD.
 
 
 
 
a)  LED ON indicates that the Battery reserve lasts for only 3 more 
minutes (selectable). 
b)  LED ON in case of over temperature or overload >125% together with 
missing Utility. 
After the timeout the Inverter
 will shut down. 
 
 
 
All LED’s ON indicate that the Battery is fully charged.  
LED a
 Yellow 
(Fixed: indicating last 25 % of Battery backup) 
(Blinking: indicating Battery backup 
 5%) 
LED b, c, d Green 
 
(EACH ONE INDICATING 25 % OF BATTERY BACKUP) 
 
 
 
LED’s ON indicate the Load status of the UPS. 
LED d
 red (
100 % load) 
LED c yellow 
(100% 
load) 
LED b green 
(66% 
load) 
LED a green 
(33% 
load) 
 
 
 
Fig. 5.2.1-1   LED’s on synoptic diagram
 
Definition of the LED’s on mimic diagram 
LED 1
  =  Input Utility Rectifier (green) 
LED 2  =  Input Utility Bypass (green) 
LED 3 = 
Rectifier 
ON 
(green) 
LED 4a = Discharging (yellow) 
LED 4b = Charging (green) 
LED 5  = Inverter ON (green) 
LED 6  =  Load on Inverter (green) 
LED 7  =  Load on Utility (green) 
LED 8  =  Output Load Voltage (green) 
LED 9  =  Manual Bypass (Q2ON (yellow) 
 
Fig. 5.2.1-2   LCD screen
 
User LCD Interface 
Consist of a LCD screen, 4 lines with 20 
characters each and six keys. It offers: 
• 
UPS operating, AC and DC metering 
information. 
• 
History of alarms and events. 
• 
Functionality can be programmed to meet 
customer needs by changing parameters.