11/38 Installation 
Guide 
SG Series 225 & 300 kVA 
3.2 DELIVERY 
 
When delivered, inspect the package integrity and the physical conditions of the 
cabinets
 carefully. 
 
In case of any damage sustained during transport, immediately inform the carrier and contact 
your local Service Center
 
detailed report of the damage is necessary for any insurance claim. 
 
 
A DAMAGED UPS MUST NEVER BE INSTALLED OR CONNECTED TO 
UTILITY OR BATTERY!
 
 
 
 
 
3.3 STORAGE 
3.3.1  Storage of the UPS 
The UPS is carefully packed for transport and storage so that it is in perfect condition when 
installed. 
Never leave a UPS outside the building and don’t store other packages on the top of the 
UPS. 
 
It is advisable to store the UPS in its original package in a dry, dust-free room, away from 
chemical substances, and with a temperature range not exceeding -13°F  (-25°C) to 131°F 
(55°C). 
 
Some important functions of the UPS, such as the customized functions, are defined by 
parameters stored in a RAM memory. 
A small backup Battery located on the Control Unit board supplies the RAM. 
If the storage time of the UPS exceeds 1 year, these functions should be verified by an 
authorized Service Center before putting the UPS into operation. 
 
 
 
3.3.2  Storage of Battery 
When the delivery includes a maintenance free Battery, keep in mind that they are subject to 
self-discharge and therefore you must recharge the Battery
 
The storage time without Battery recharge depends on the temperature of the storage site. 
 
The optimal temperature for Battery storage is 68°F (20°C) to 77°F (25°C). 
 
Recharge stored maintenance free Battery every: 
6 months when the storage temperature is 68°F (20°C) 
3 months when the storage temperature is 86°F (30°C) 
2 months when the storage temperature is 95°F (35°C)