Hitachi SJ300 Series Manual De Usuario

Descargar
Página de 294
“C” Group: Intelligent Terminal Functions
Configur
ing Dr
iv
P
a
ra
meters
3–48
The input logic convention is programmable for each of the six inputs. Most inputs default to 
normally open (active high), but you can select normally closed (active low) in order to invert 
the sense of the logic.
NOTE: An input terminal configured for option code 18 ([RS] Reset command) cannot be 
configured for normally closed operation.
“C” Function
Run 
Mode
Edit
Lo Hi
Defaults
Units
SRW Display
Func.
Code
Name
Description
–FE
(EU)
–FU
(US)
–FR
(JP)
C011
Terminal [1] active state
Select logic convention, 
two option codes:
00 normally open N.O.
01 normally closed N.C.
✘ ✔
00
00
00
>C011 IN-TM
O/C-1         NO
C012
Terminal [2] active state
✘ ✔
00
00
00
>C012 IN-TM
O/C-2         NO
C013
Terminal [3] active state
✘ ✔
00
00
00
>C013 IN-TM
O/C-3         NO
C014
Terminal [4] active state
✘ ✔
00
00
00
>C014 IN-TM
O/C-4         NO
C015
Terminal [5] active state
✘ ✔
00
00
00
>C015 IN-TM
O/C-5         NO
C016
Terminal [6] active state
✘ ✔
00
01
00
>C016 IN-TM
O/C-6         NO
C017
Terminal [7] active state
✘ ✔
00
00
00
>C017 IN-TM
O/C-7         NO
C018
Terminal [8] active state
✘ ✔
00
00
00
>C018 IN-TM
O/C-8         NO
C019
Terminal [FW] active 
state
✘ ✔
00
00
00
>C019 IN-TM
O/C-FW        NO