T7351 COMMERCIAL PROGRAMMABLE THERMOSTAT
11
62-0258
Fig. 9. Typical hookup of T7350F2010 in three-stage heat and three-stage cool conventional system
with one transformer.
TROUBLESHOOTING GUIDE (TABLE 7)
Table 7. Troubleshooting Information.
Symptom
Possible Cause
Action
Display will not 
come on.
Thermostat is not being powered.
Check that X terminal is connected to the system transformer.
Check for 24 Vac between X and RH terminals.
If missing 24 Vac:
• Check if circuit breaker is tripped; if so, reset circuit breaker.
• Check if system fuse is blown; if so, replace fuse.
• Check if the HVAC equipment power switch is in the Off 
position; if so, set to the On position.
• Check wiring between thermostat and HVAC equipment. 
Replace broken wires and tighten loose connections.
If 24 Vac is present, proceed with troubleshooting.
Temperature 
display is 
incorrect.
Thermostat is configured for °F or 
°C display.
Press both Run Schedule and Copy, then reconfigure the 
display.
Bad thermostat location.
Relocate the thermostat.
Display shows three dashes and a 
degree sign (all systems shut 
down).
T7351 is set for remote sensing and sensor is missing or circuit 
is either open or shorted.
Temperature 
settings will not 
change.
(Example: 
Cannot set 
heating higher or 
cooling lower.)
Upper or lower temperature limits 
were reached.
Check the temperature setpoints:
• Heating limits are 40 to 90°F (7 to 31°C)
• Cooling limits are 45 to 99°F (9 to 37°C)
Occupied setpoint temperature 
range stops were configured.
Check setpoint stops. If necessary, reconfigure the stop(s).
Keypad is locked. When a locked 
key is pressed, LOCKED appears 
momentarily on the LCD.
Press both Run Schedule and Copy, then change keypad lock 
level.
Room 
temperature is 
out of control.
Remote temperature sensing is not 
working.
Check all remote sensors.
POWER SUPPLY.  PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
ENSURE TRANSFORMER IS SIZED TO HANDLE THE LOAD.
HEAT/COOL SYSTEMS WITH ONE TRANSFORMER REQUIRE THE FACTORY-INSTALLED JUMPER.
USE ECONOMIZER INSTRUCTIONS FOR INSTALLATION DIRECTIONS.
1
M25319
2
3
2
3
4
 
RC
AUX
X
SUBBASE
 W1
G
T7770 REMOTE SENSOR
Y1
 
 
W3/Y4 Y3
W2
Y2
AUX
RH
T5
T6
T7
T4
T3
DISCHARGE
AIR
SENSOR
OUTDOOR
AIR
SENSOR
MOTION
SENSOR
HUMIDITY
SENSOR
M
OS
OS
AS
AS
M
HC
HP
HS
1
4
L1
(HOT)
L2
COMPRESSOR
CONTACTOR 1
COMPRESSOR
CONTACTOR 2
HEAT
RELAY 1
1
2
3
4
5
6
7
8
9
FAN
RELAY
ECONOMIZER
HEAT
RELAY 2
COMPRESSOR
CONTACTOR 3
HEAT
RELAY 3