C7400S ENTHALPY SYLK BUS SENSOR
3
62-0332—03
WIRING
All wiring must comply with applicable electrical codes and 
ordinances, or as specified on installation wiring diagrams.
WARNING
Electrical Shock Hazard.
Can cause severe injury, death or property 
damage.
Disconnect power supply before beginning wiring, or 
making wiring connections, to prevent electrical shock 
or equipment damage.
CAUTION
Equipment Damage Hazard.
Electrostatic discharge can short equipment 
circuitry.
Ensure that you are properly grounded before 
handling the sensor.
Prepare wiring as follows:
1. Strip 1/2 in. (13 mm) insulation from the conductor.
2. Cut a single wire to 3/16 in. (5 mm). Insert the wire in 
the required terminal location and tighten the screw.
3. Pull on each wire in all terminals to check for good 
mechanical connection.
Sylk Bus Sensor Wiring
Use Fig. 4 and Table 1 to locate the wiring terminals for each 
Sylk Bus sensor.
Use Fig. 4 and Table 2 to set the DIP switches for the desired 
use of the sensor.
Fig. 4. Sylk Bus sensor DIP switches.
CHECKOUT
Refer to the JADE™ Economizer Module (Model W7220) 
Installation Instructions (Honeywell form 62-0331).
TROUBLESHOOTING
Refer to the JADE™ Economizer Module (Model W7220) 
Installation Instructions (Honeywell form 62-0331).
DIP 
SWITCH
LABEL
M32271
SYLK BUS 
TERMINALS 
(1 AND 2)
DIP 
SWITCHES
(3)
SYLK BUS 
2 PIN “EURO” 
CONNECTOR
Table 1. SYLK Bus Sensor Wiring Terminations
a
.
a
Terminals are polarity insensitive.
Terminal
Type
Description
Nbr
Label
1
S-BUS SYLK Bus Sylk Bus Communications 
(Sensor Bus)
2
S-BUS SYLK Bus Sylk Bus Communications 
(Sensor Bus)
Table 2. SYLK Bus Sensor DIP Switch Settings.
Use
DIP Switch Positions for Switches 1, 2, & 3
1
2
3
DA
a
a
DA = Discharge Air 
OFF
ON
OFF
RA
b
b
RA = Return Air 
ON
OFF
OFF
OA
c
c
OA = Outside Air
OFF
OFF
OFF