TB6575/TB8575 SUITEPRO™ DIGITAL FAN COIL THERMOSTATS
62-0278—07
18
Both the heating and 
cooling equipment are 
running at the same 
time. 
Incorrect System Type 
selected.
Check that the Installer Setup code #2 (System Type) value 
matches the installed heating and/or cooling equipment. 
Heating and cooling wires 
are shorted together. 
Separate the shorted heating and cooling wires.
Cooling does not turn 
on (Cool On is solid in 
the display). 
Cooling equipment failure.  For TB6575A/B/C:
1. Check for 120/240/277 Vac at the equipment between power 
and common, (terminals L and N).
2. Check for 120/240/277 Vac between the cool (Y) and com-
mon (N) terminals. If 120/240/277 Vac is present, the ther-
mostat is functional.
For TB8575A:
1. Check for 24 Vac at the equipment on the secondary side of 
the transformer between power and common (terminals R 
and C).
2. Check for 24 Vac between the cool terminal (Y) and trans-
former common. If 24 Vac is present, the thermostat is func-
tional. 
If voltage is present, check the cooling equipment to find the cause 
of the problem.
Loose connection or 
broken wire between 
thermostat and cooling 
equipment. 
For TB6575A/B/C:
Check for 120/240/277 Vac between the cool (Y) and common 
(N) terminals. 
For TB8575A:
Check for 24 Vac between the cool terminal (Y) and transformer 
common. 
If voltage is not present, check the wire connection (loose or 
broken) between the thermostat and the cooling equipment. 
Fan does not turn on 
in a call for Heat. 
Wiring or connection 
failure
Check wiring and make sure the connection is correct.
Cannot select fan 
speed.
Fan Control Type 
selection is incorrect.
Check that the Installer Setup code #9 (Fan Control) value is set to 
zero (0). 
Heating equipment is 
running in the Cool 
mode. 
Incorrect System Type 
configured.
Check that the Installer Setup code #2 (System Type) value 
matches the installed heating and/or cooling equipment. 
Heating equipment 
does not turn off and 
heat temperature 
setting is set below 
room temperature 
(Heat On is not in the 
display). 
Incorrect System Type 
configured.
Check that the Installer Setup code #2 (System Type) value 
matches the installed heating and/or cooling equipment. 
Cannot set the system 
setting to Heat. 
System Type (Installer 
Setup code #2) is set to 
Cool Only (value = 1). 
Set the Installer Setup code #2 value to match the installed heating 
and/or cooling equipment. 
Cannot set the system 
setting to Cool. 
System Type (Installer 
Setup code #2) is set to 
Heat Only (value = 0).
Set the Installer Setup code #2 value to match the installed heating 
and/or cooling equipment. 
Heat On is not in the 
display. 
System Type setting is not 
set to Heat and/or the 
temperature setting is not 
set above the room 
temperature. 
Set the Installer Setup code #2 to Heat and set the temperature 
setting above the room temperature. 
Cool On is not in the 
display. 
System Type setting is not 
set to Cool and/or the 
temperature setting is not 
set below the room 
temperature. 
Set the Installer Setup code #2 to Cool and set the temperature 
setting below the room temperature. 
Remote sensor does 
not display 
temperatures
Incorrect IS code.
Set the Installer Setup code #4 to Remote (value = 1).
Sensor is not compatible. The remote sensor must be TR21 or compatible 20K NTC.
Table 8. Troubleshooting. (Continued)
Symptom Possible 
Cause 
Action