ML4202, ML4302, ML4702, ML4802, ML8202, ML8302 FAST-ACTING, TWO-POSITION ACTUATORS
62-0194—3
2
Controller Type:
ML4202, ML4302: Line voltage (120 Vac), two-position, spst 
(Series 40).
ML4702, ML4802: Line voltage (230 Vac), two-position, spst 
(Series 40).
ML8202, ML8302: Low voltage (24 Vac), two-position, spst 
(Series 80).
Accessories:
201391 Shaft Adapter for 3/8 in. shafts (not supplied with 
actuator).
205649 Mounting Bracket (not supplied with actuator).
32003532-005 Dual Auxiliary Switch Package for high-
temperature applications.
Table 2. Approvals.
WARNING
Electrical Power Hazard.
Line voltage can cause death or serious injury
and short equipment circuitry.
Disconnect power supply before installation.
CAUTION
Electrical Shock or Equipment Damage Hazard.
Low voltage can shock individuals or short 
equipment circuitry.
Disconnect power supply before installation.
CAUTION
Equipment Damage Hazard.
Tightly securing actuator to damper housing can 
damage actuator.
Mount actuator to allow it to float along its vertical axis.
CAUTION
Actuator Damage Hazard.
Using actuator as shaft bearing causes device 
damage.
Use actuator only to supply rotational torque. Avoid 
any side loads to actuator output coupling bearings.
IMPORTANT
1. All wiring must comply with local electrical codes, 
ordinances and regulations.
2. Voltage and frequency of transformer used with 
ML8202 and ML8302 must correspond with the 
characteristics of power supply and actuator.
3. Use wires rated for at least 75°C (167°F).
4. For actuators with a product date code before 0527, 
a power break of less than two seconds can cause 
the actuator to spring-return 5 degrees or less and 
remain in place until a power break of longer dura-
tion. For actuators with a product date code of 0527 
or after, a power break of any duration will cause the 
actuator to spring-return and be able to drive imme-
diately when power is reapplied.
Fig. 1. ML4202, ML4302, ML4702, ML4802, ML8202, 
ML8302 dimensional drawing in in. (mm).
Fig. 2. Typical 24 Vac wiring.
Fig. 3. Typical 120 Vac wiring.
Fig. 4. Typical 230 Vac wiring.
ML4202 
ML4302
ML4702 
ML4802
ML8202 
ML8302
UL/cUL
X
X
X
UL873 Plenum Rating, File 
No. E4436; Guide No. XAPX.
X
X
X
CE
X
X
C-TICK
X
1 (25)
5/8 
(17)
6-3/8
(161)
7-1/2 
(192)
4 (102)
7/8 (22)
/ (
)
2 (51)
3-5/16 (84)
1/16 (2
L1 
24 VAC
L2
RED
BLACK
M17585A
(   )
(   )
L1 
120 VAC
L2
WHITE
BLACK
M17589A
(   )
(   )
L1 
230 VAC
L2
BLUE
BROWN
M17588A
(   )
(   )