Fagor nc-200 pb Instruccion De Instalación

Descargar
Página de 58
 NC-200 PB  -  Installation Manual - Page: 51
Analog input / outputs <Ana
In this mode, it is possible to force a value to the analog outputs in order to move
the axes and set reference values in parameters PAR44 through PAR48.
·
Select the 
 or 
 axis
The enable signal of the relevant axis is activated.
·
Every time 
 or  
 is pressed, the value is increased or decreased in 0.01V
within a range of ±10V.
·
To force a particular analog voltage, press: 
 [decimal value] 
To reset the analog voltage, press 
 or 
If it is a B model and a potentiometric scale has been installed,
PAR64.4=1, 65.4 = 1, it can read the analog input at pin 18:
·
Select 
While moving the ram or the base, it is possible to compare the
maximum/minimum values of the cursor.
<Auto> 
It is enabled in automatic mode to fine tune the values of the two param-
eters involved in the adjustment of the axes:
<Vmin> 
 to adjust the minimum voltage.
·
Select the 
  or 
 axis
An auxiliary mode is available to operate with the axis in open loop and display
the offsets of the drives on the 1st display.
Adjust it until the offset is stabilized at "0" and confirm it by pressing 
·
This unit generates an increasing positive voltage (command) to move the
axis. This process is interrupted when it accumulates more than 100 feedback
pulses and  it set PAR44 with the current voltage value.
This process is repeated with an increasing negative voltage for PAR45.