Crestron electronic CEN-UPS1250 Manual De Usuario

Descargar
Página de 40
Crestron CEN-UPS1250 
 
Uninterruptible Power Supply
 
RoomView
®
 and Control System Integration 
Monitoring and operation of the CEN-UPS1250 extends beyond its front panel, 
providing direct communication with Crestron’s RoomView Remote Asset 
Management Software as well as with Ethernet enabled 2-Series control systems. 
The CEN-UPS1250 notifies RoomView whenever it switches to battery backup and 
warns if the battery is low or overloaded. It also reports which outlet banks are on, as 
well as the line voltage, output voltage, frequency, voltage regulation status, system 
load, internal temperature, ambient temperature and humidity and battery condition. 
Centralized monitoring and logging via RoomView provides an invaluable resource 
for quickly resolving power line problems and maintaining batteries. 
Built-in Logging 
In addition to RoomView, the CEN-UPS1250 also supports onboard timestamp 
logging. Data can be set to log every 1 to 60 minutes with sufficient memory for at 
least 30 days of history, recording the load, battery condition, line voltage, outlet 
on/off status and environmental conditions. Instantaneous events such as switching 
to battery, low battery warnings and self tests are also logged. 
Rack Mountable 
A heavy duty rack mount hardware kit is provided to mount the unit into any EIA 
standard four post 19” equipment rack up to 28” deep. The feet on the bottom of the 
unit can be unscrewed and removed to save space when the unit is rack-mounted. 
Specifications 
Specifications for the CEN-UPS1250 are listed in the following table. 
CEN-UPS1250 Specifications 
SPECIFICATION DETAILS 
UPS/Power Conditioner 
 
 
Output Power Capacity 
1250 Watts (1440 VA) @ 120 Volts AC 
nominal 
 
Efficiency 
90% at full load 
 
Output Voltage Distortion 
<5% at full load 
 
Output Frequency 
47 to 63 Hz (sync to line power input) 
 
Waveform Type 
Sine wave 
 Transfer 
Time 
7 ms typical, 10 ms maximum during 
blackout 
 
Power Line Surge Protection 
Rated for 4080 Joules 
 Filtering 
Full time multi-pole noise filtering, 5% IEEE 
surge let-thru, zero clamping response 
time, meets UL 1449 Dataline protection 
 Voltage 
Regulation 
Performs voltage boost or trim to maintain 
120 V nominal output 
 
Maximum Output Current 
12 Amps per outlet, 12 Amps total 
Power Requirements 
 
 Input 
Voltage 
92 to 142 Volts AC, 120 Volts nominal 
 Input 
Frequency 
47 to 63 Hz 
 
Maximum Input Current 
12 Amps (when fed from 15 Amp circuit) 
(Continued on following page) 
Operations & Installation Guide – DOC. 6635A 
Uninterruptible Power Supply: CEN-UPS1250  
  3