DSC pc1616 Manual De Usuario

Descargar
Página de 64
Section 1: Installation & Wiring
1
Section 1: Installation & Wiring
This Installation Guide provides the basic installation, wiring and programming information required to program the PowerSeries PC1616, 
PC1832 and PC1864 control panels. 
 This guide shall be used in conjunction with the PowerSeries PC1616/1832/1864 Reference Manual which 
can be obtained from your local dealer or downloaded from the DSC web site at www.dsc.com.
 
 All necessary information required to meet UL Listing requirements is included in this document.
Technical Summary
Installation
FEATURES
PC1616
PC1832
PC1864
OUT Of THE BOX
On-board Zones
8
8
Qty 1 
Qty 1 
Qty 1 
Qty 1 
Qty 2 
Qty 1
 
Qty 4 
Qty 16 
Qty 1
 
Qty 1
 
Qty 1 
Qty 1 
Cabinet
PC Module
Installation guide
User manual
Cabinet Label
Cabinet Door Plug
Standoffs
5.6K
Ω
 Resistors
2.2K
Ω
 Resistor
1.0K
Ω
 Resistor
10
Ω
 Resistor
Grounding Kit
Hardwired Zones
16 (1xPC5108)
32(3xPC5108)
64 (7xPC5108)
Wireless Zones
16
32
32
Keypad Zone Support
On-board PGM Outputs
PGM 1 - 50mA
PGM 2 - 300mA
PGM 1 - 50mA
PGM 2 - 300mA
PGM 1, 3, 4 - 50mA
PGM 2 - 300mA
PGM Expansion
8x50mA (PC5208)
4x500 mA (PC5204)
8x50mA (PC5208)
4x500 mA (PC5204)
8x50mA (PC5208)
4x500 mA (PC5204)
Keypads
8
8
8
Partitions
2
4
8
SPECIFICATIONS
Temp Range ......... 0°C-49°C (32°F-120°F)
Humidity (Max) ............................ 93%R.H.
Power Supply ........ 16.5VAC/40VA @60Hz
Current Draw (Panel)...........110mA (nom.)
Aux+ Output ........... 11.1-12.6VDC/700mA
Bell Output.............. 11.1-12.6VDC/700mA
User Codes
32 + Master Codes
32 + Master Codes
32 + Master Codes
Event Buffer
500 Events
500 Events
500 Events
Transformer Required
16.5VAC/40VA
16.5VAC/40VA
16.5VAC/40VA
Battery Required
4Ah / 7Ah/14AHr
4Ah / 7Ah/14AHr
4Ah / 7Ah/14AHr
Bell Output
12V/700 mA (cont)
12V/700 mA (cont)
12V/700 mA (cont)
COMPATIBLE DEVICES
Keypads (
Backward compatible with all PowerSeries keypads)
Modules
PK5500 Keypad ............................................................... 125mA (max.)
PK5501 Keypad ............................................................... 125mA (max.)
PK5508 LED Keypad ....................................................... 125mA (max.)
PK5516 LED Keypad ....................................................... 125mA (max.)
PC5532Z LED Keypad ..................................................... 125mA (max.)
LCD5511 Fixed Message LCD Keypad ............................  85mA (max.)
LED5511Z 8-zone LED Keypad  ...................................... 100mA (max.)
Cabinets
PC5003C...........................................222x298x78mm (11.3x11.7x3.0in)
PC500C (residential burg only) ...........213x235x78mm (8.4x9.25x3.0in)
PC4050CAR (UL commercial burg)305x 376x124mm (12.0x14.8x4.9in)
CMC-1 (UL commercial burg) ...........287x297x76mm (11.3x11.7x3.0in)
Refer to the Reference Manual for alternate control cabinets
T-Link TL150*TL-250/TL300 .......................................... 275/350mA
PC5100 2-wire Interface ..........  40mA plus devices to 170mA max.
PC5132-433 Wireless Receiver  ........................................... 125mA
RF5108-433 Wireless Receiver  ........................................... 125mA
PC5108 Zone Expander ......................................................... 30mA
PC5200 Power Supply ............................................................ 20mA
PC5204 Power Supply with 4 Programmable Outputs  .......... 30mA
PC5208 Low Current Programmable Output Module  ............ 50mA
PC5400 Printer/DVAC Module ............................................... 65mA
PC5401 Bi-Directional RS232 Module (Not UL Listed)  .......... 65mA
Escort5580 Telephone Interface Module  ............................. 130mA
*The T-Link TL-150 is not UL/ULC listed
Refer to the Reference Manual for additional devices.
Classified in Accordance with ANSI/SIA CP-01-2000 (SIA-FAR)
Begin the installation by mounting additional modules in the cabinet using the standoffs provided, then mount the cabinet in a dry 
protected area with access to unswitched AC power. 
Install Hardware in the sequence indicated in the following pages. Do NOT apply power until installation is complete.
All wiring entry points are designated by arrows. All circuits are classified UL power limited except for 
the battery leads. Minimum 1/4” (6.4mm) separation must be maintained at all points between power
limited and non-power limited wiring and connections.