Honeywell V8944C Manual De Usuario

Descargar
Página de 12
V4943/V8943B,C,N; V4944/V8944B,C,L,N REGULATING DIAPHRAGM GAS VALVES
65-0214—08
6
Fig. 7. Capacity vs. pressure drop of LP Gas
curves for 1-1/4 in. valve.
Fig. 8. Capacity vs. pressure drop of LP Gas
curves for 1-1/2 in. valve.
Fig. 9. Capacity vs. pressure drop of LP Gas
curves for 2 in. valve.
To size two identical valves piped in series:
1. Find the cf/h for the type of gas used.
2. Consider both valves as one unit. Determine the 
maximum pressure drop across the one unit.
3. Find the pressure drop across the first valve by assuming 
it to be 45 percent of the total pressure drop.
4. Find the valve size from Figs. 2–9.
5. The second valve will be the same size as the first valve.
INSTALLATION
WARNING
Explosion hazard.
Can cause serious injury, death or equipment 
damage.
Installation and service by trained professionals only. 
Exceeding the pressure rating or use of unspecified 
fuel can lead to improper operation of the valve and can 
create an explosion hazard. Property damage, severe 
bodily injury or death can result.
When installed in the Commonwealth of 
Massachusetts, the installation and servicing of this 
product must be done by a licensed gas fitter or 
plumber.
Consult specifications before installing valve.
M23381
1.25 INCH V4/8944C/L REGULATION AREA
0.1
1
10
100
100
1000
10000
FLOW LP GAS (CFH)
PRESSURE DROP (IN. WC)
ANY PO
PO < 5.5 IN.
M23382
1.5 INCH V4/8944C/L REGULATION AREA
0.1
1
10
100
100
1000
10000
FLOW LP GAS (CFH)
PRESSURE DROP (IN. WC)
ANY PO
PO < 8 IN.
M23383
2 INCH V4/8944C/L REGULATION AREA
0.1
1
10
100
100
1000
10000
FLOW LP GAS (CFH)
PRESSURE DROP (IN. WC)
ANY PO
PO < 8 IN.