Página de 32
3.     After  all  refrigerant  has  been  recovered,  disconnect  
suction and discharge lines from the compressor and  
remove compressor. Be certain to have both suction  
and discharge process tubes open to atmosphere. 
4.     Carefully pour a small amount of oil from the suction  
stub  of  the  defective  compressor  into  a  clean 
container.  
9.      Evacuate the system with a good vacuum pump capable    
of a final vacuum of 200 microns or less. The system 
should be evacuated through both liquid line and suction 
line gauge ports. While the unit is being evacuated, seal 
all openings on the defective compressor. Compressor 
manufacturers will void warranties on units received not 
properly sealed. Do not distort the manufacturers tube 
connections.   
10.    Recharge  the  system  with  the  correct  amount  of 
  refrigerant.  The  proper  refrigerant  charge  will  be 
   found on the unit rating plate. The use of an accurate
         measuring device, such as a charging cylinder,
         electronic scales or similar device is necessary.
 
5.     Using an acid test kit (one shot or conventional kit), test  
the  oil  for  acid  content  according  to  the  instructions  
with the kit. 
6.   If any evidence of a burnout is found, no matter how  
slight, the system will need to be cleaned up following  
proper procedures. 
7.    Install the replacement compressor. 
8.  Pressurize with a combination of R-410A and nitrogen  
      and  leak  test  all  connections  with  an  electronic  or  
      Halide  leak  detector.  Recover  refrigerant  and  repair 
      any leaks found. 
 
Repeat Step 8 to insure no more leaks are present.
The use of nitrogen requires a pressure
regulator. Follow all safety procedures and 
wear protective safety clothing etc. 
Failure to follow proper safety procedures 
result in serious injury or death. 
WARNING
EXPLOSION HAZARD 
Proper safety procedures must be followed, 
and proper protective clothing must be worn 
when working with liquid refrigerant.
Failure to follow these procedures could 
result in minor to moderate injury.
CAUTION
FREEZE HAZARD 
20
ELECTRIC SHOCK HAZARD 
WARNING
Turn off electric power before service or 
installation.
Failure to do so may result in personal injury, 
or death.
Sealed Refrigeration System contains refrigerant 
and oil under high pressure.
Proper safety procedures must be followed, 
and proper protective clothing must be worn 
when working with refrigerants.
Failure  to  follow  these  procedures  could 
result in serious injury or death. 
WARNING
HIGH PRESSURE HAZARD 
The use of nitrogen requires a pressure
regulator. Follow all safety procedures and 
wear protective safety clothing etc. 
Failure to follow proper safety procedures 
result in serious injury or death. 
WARNING
EXPLOSION HAZARD 
1.
2.
3.
4.
5.
Recover all refrigerant and oil from the system.  
 
Remove compressor, capillary tube and filter drier  
from the system.  
 
Flush evaporator condenser and all connecting 
tubing with dry nitrogen or equivalent. Use approved 
flushing agent to remove all contamination from 
system. Inspect suction and discharge line for 
carbon deposits. Remove and clean if necessary. 
Ensure all acid is neutralized. 
 
Reassemble the system, including new drier strainer 
and capillary tube. 
Proceed with step 8-10 on previous section. 
SPECIAL PROCEDURE IN THE CASE OF MOTOR 
COMPRESSOR BURNOUT