Pilot will not light.
-  check if pilot can be lit by a match
-  check that the wire is connected to the push button ignitor.
-  check if the push button ignitor needs tightening.
-  replace the wire if the wire insulation is broken or frayed.
-  replace the electrode if the ceramic insulator is cracked or broken.
-  replace the push button ignitor.
 No spark at pilot burner
-  fill the tank.
Out of propane gas
Spark  gap  is  incorrect
-  spark gap should be 0.150" to 0.175" (5/32" to 11/64" approx.) from
the electrode tip and the pilot burner. To ensure proper electrode
location, tighten securing nut (finger tight plus 1/4 turn).
No gas at the pilot burner
-  check that the manual valve is turned on.
-  check the pilot orifice for blockage.
-  replace the valve.
-  call the gas distributor.
Main burner goes
out; pilot stays on.
Pilot flame is not large
enough or not engulfing the
thermopile
-  turn up pilot flame.
- replace pilot assembly.
Thermopile shorting
- clean thermopile connection to the valve. Reconnect.
- replace thermopile / valve.
Remote wall switch wire is
too long; too much resist-
ance in the system.
-  shorten wire to correct length or wire gauge.
Faulty thermostat or switch.
-    replace.
5" flexible vent has become
disconnected from fireplace.
Pilot goes out when
the gas knob is re-
leased.
The gas valve has
an interlock device
which will not allow
the pilot burner to
be lit until the ther-
mocouple has
cooled. Allow ap-
proximately 60
seconds for the
thermocouple to
cool.
System is not correctly
purged.
-  purge the gas line with the glass door removed.
Out of propane gas.
-  fill the tank.
Pilot flame is not large
enough
-  turn up the pilot flame.
-  gently twist the pilot head to improve the flame pattern around the
thermocouple.
Pilot flame is not engulfing
the thermocouple.
Thermocouple shorting /
faulty.
-  loosen and tighten thermocouple.
-  clean thermocouple and valve connection.
-  replace thermocouple.
-  replace valve.
Faulty valve.
-  replace.
Pilot burning; no
gas to main
burner; gas knob
is on 'HI'; wall
switch / thermostat
is on.
Themostat or switch is de-
fective.
-  connect a jumper wire across the wall switch terminals; if main
burner lights, replace switch / thermostat.
Main burner orifice is plugged.
-    remove stoppage in orifice.
Faulty valve.
-  replace.
Wall switch wiring is defec-
tive.
-  disconnect the switch wires & connect a jumper wire across termi-
nals 1 & 3; if the main burner lights, check the wires for defects and
/ or replace wires.
Main burner goes
out; pilot goes out.
Refer to "MAIN BURNER GOES OUT; PILOT STAYS ON"
Vent is blocked
Vent is re-circulating
-  check for vent blockage.
-  check joint seals and installation.
-  re-attach to fireplace.
TROUBLE SHOOTING GUIDE
SYMPTOM
PROBLEM
TEST SOLUTION
B
EFORE
 
ATTEMPTING
 
TO
 
TROUBLESHOOT
PURGE
 
YOUR
 
UNIT
 
AND
 
INITIALLY
 
LIGHT
 
THE
 
PILOT
 
AND
 
THE
 
MAIN
 
BURNER
 
WITH
 
THE
 
GLASS
 
DOOR
 
REMOVED
.