Equivalent Vent Length (EVL) 
The longer the run of pipe in your installation (both with inserts and 
freestandings), the more restriction there is in the system. Therefore, 
larger diameter pipe should be used. 
• 
Use 4” pipe if you have more than 15 feet of equivalent vent 
length. 
• 
Horizontal runs shall not exceed 10 feet of EVL. 
• 
It is recommended that vertical runs be a minimum of 8 feet. 
• 
To calculate EVL, use the following conversions: 
 
90º elbow or “T”  
= 5 equivalent feet 
45º elbow 
 
= 3 equivalent feet 
Horizontal Pipe Run 
= 1 equivalent foot per actual foot 
Vertical Pipe Run 
= 0.5 equivalent foot per actual foot 
NOTE: At altitudes above 3,000 feet, we suggest the use of 4” 
diameter vent at an EVL of 7 feet or more. 
P4000 INSTALLATION 
A. 
HORIZONTALLY THROUGH WALL (refer to Figure 6) 
 
NOTE: See “VENTING” and follow L-Vent chimney manufacturer’s 
instructions. 
 
1. 
Position stove, adhering to clearances shown in Figures 1 & 2. 
 
2. 
Locate position of hole in wall; directly behind stove exhaust vent 
(refer to figure 4). 
 
3. 
Always maintain 3” clearance from combustible materials. 
 
4. 
Install L-Vent wall thimble per L-Vent manufacturer’s instructions. 
 
5. 
Attach enough piping to penetrate and extend at least 6” beyond 
exterior walls. An 8-foot vertical pipe run is suggested where 
possible to reduce the possibility of smoke spillage in the event 
of a loss of negative pressure. 
 
6. 
Attach cap and seal outside wall thimbles with non-hardening 
waterproof mastic. 
 
7. 
Termination should not be located so that hot exhaust gases can 
ignite trees, shrubs, or grasses or be a hazard to children. 
Exhaust gases can reach temperatures of 500ºF and cause 
serious burns if touched. 
 
 
 
 
Locate terminations: a) not less than 3 feet above any forced air 
inlet located within 10 feet; b) not less than 4 feet below or 
horizontally from, or one foot above, any door, window or gravity 
air inlet into any building; c) not less than two feet from an adjacent 
building and not less than 7 feet above grade when located 
adjacent to a public walkway. Mobile home installations must use a 
spark arrester. 
FIGURE 6 
INSTALLATION