Puls UC10.242 DIN-Rail UPS Guia De Especificaciones
![Puls](https://files.manualsbrain.com/attachments/f7041454b866cfdaa2ab969e2fceed93f951f2f9/common/fit/150/50/2534d33282a162a3c2687862aa5026f5d26de2af0500a4f43b3b09ee366e/brand_logo.gif)
UC10.241, UC10.242
UC-Series
24V,
15A,
C
APACITOR
-
BASED
B
UFFER
M
ODULES
5. C
HARGING
During charging, the buffer module consumes additional current from the input. See chapter “Input”.
When charging is completed, the “Ready LED” stops flashing and is on solid and the “Ready relay contact” closes.
UC10.241 UC10.242
Charging time
initial
initial
charging
*)
typ.
16 minutes
32 minutes
when capacitor is completely discharged
Charging time
recharging
recharging
**)
typ.
1 minute 50s
1 minute 50s
after discharging with 10A for 10s
typ.
3 minutes 50s
7 minutes 40s
after discharging with 10A until buffering
stops
stops
typ.
4 minutes 40s
9 minutes 40s
after discharging with 5A until buffering
stops
stops
typ.
5 minutes 40s
11 minutes 15s
after discharging with 1A until buffering
stops
stops
Allowed number of charging /
discharging cycles
discharging cycles
no limitation
no limitation
*)
Initial charging means that no input voltage was applied for several hours or longer and the capacitor is completely discharged by the
internal electronics.
internal electronics.
**) Recharging means that the electronics inside the buffer module has not completely discharged the capacitor. The values in the table
apply when the input voltage is applied immediately after buffering has stopped.
Note:
At the end of the charging process the active balancing circuit reduces the charging current periodically, which can be
seen as current oscillations on the input current.
At the end of the charging process the active balancing circuit reduces the charging current periodically, which can be
seen as current oscillations on the input current.
Apr. 2014 / Rev. 2.0 DS-UC10.241-EN (REVC)
All parameters are specified at 24V, 10A output current, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
All parameters are specified at 24V, 10A output current, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany