Puls UC10.242 DIN-Rail UPS Guia De Especificaciones

Descargar
Página de 27
 
 
UC10.241, UC10.242
 
 
UC-Series 
24V,
 
15A,
 
C
APACITOR
-
BASED 
B
UFFER 
M
ODULES
 
 
 
5.  C
HARGING
 
 
During charging, the buffer module consumes additional current from the input. See chapter “Input”. 
When charging is completed, the “Ready LED” stops flashing and is on solid and the “Ready relay contact” closes. 
 
 
 
UC10.241 UC10.242   
Charging time  
 initial 
charging
*)
 
typ. 
16 minutes 
32 minutes 
when capacitor is completely discharged 
Charging time  
 recharging
**)
 
typ. 
1 minute 50s 
1 minute 50s 
after discharging with 10A for 10s 
 
typ. 
3 minutes 50s 
7 minutes 40s 
after discharging with 10A until buffering 
stops 
 
typ. 
4 minutes 40s 
9 minutes 40s 
after discharging with 5A until buffering 
stops 
 
typ. 
5 minutes 40s 
11 minutes 15s 
after discharging with 1A until buffering 
stops 
Allowed number of charging / 
discharging cycles 
 
no limitation 
no limitation 
 
*) 
Initial charging means that no input voltage was applied for several hours or longer and the capacitor is completely discharged by the 
internal electronics. 
**)  Recharging means that the electronics inside the buffer module has not completely discharged the capacitor. The values in the table 
apply when the input voltage is applied immediately after buffering has stopped. 
Note: 
At the end of the charging process the active balancing circuit reduces the charging current periodically, which can be 
seen as current oscillations on the input current. 
 
Apr. 2014 / Rev. 2.0 DS-UC10.241-EN (REVC) 
All parameters are specified at 24V, 10A output current, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. 
www.pulspower.com   Phone +49 89 9278 0    Germany 
7/27